The bidirectional control terminals X210A.1/ X210A.2 can be used as a voltage
output or voltage input. By connecting an external power supply of DC 24 V
±10% to terminals X210A.1/X210A.2, the function of inputs and outputs as
well as the communication can be parameterized and maintained, even when
mains voltage is off.
Requirements to be met by external power supply
Input voltage range
Rated input current
Peak inrush current
External fuse
Safety
GB
4.3.3 Control terminal X10
Term.
1 ... 3
Relay output, floating change-over contact, response time approx. 40 ms,
maximum contact load:
4.3.4
WARNING!
When two or more devices are connected, CAN-Low, CAN-High and
GND
Without GND
Terminals X410A/X410B/X412 are specified for their specific volt-
age levels. Voltage levels exceeding the specified levels should be
avoided. Higher voltages can damage the module.
108
DC 24 V ±10%
Max. 1.1 A
Typically: < 25 A
Via standard fuse elements for rated current, char-
acteristic: slow
Safety extra low voltage (SELV) according to
EN 61800-5-1
Control terminal X10
make contact: AC 5 A / 240 V, DC 5 A (ohmic) / 24 V
break contact:
Automation Interface EM-AUT (X410A, X410B,
X412)
must be connected.
CAN
connection, telegram abortions can occur.
CAN
CAUTION
Quick Start Guide ANG
Relay output X10
S3OUT Parameterizable relay output
Description
AC 3 A / 240 V, DC 1 A (ohmic) / 24 V
07/20