8
Technical data
CAUTION
Device defect and motor defect
The recommended motor shaft power indicated in the technical
data applies to IE1 motors only. Ignoring the possible DC-link cur-
rents may decrease the motor product life and may damage the
inverter.
•
•
GB
General technical data (may differ for some sizes)
Output, motor side
Output voltage
Protection
Rotary field frequency
Switching frequency
Input, mains side
Mains voltage
Mains frequency
Ambient conditions
Coolant air temperature
Operating conditions
Storage temperature
Transport temperature
Rel. humidity
Mechanical
Form of assembly
Ingress protection rating
If required by the customer, the switching frequency may be in-
creased if the output current is reduced at the same time. Comply
with the applicable standards and regulations for this operating
point.
130
Always verify the applicable operation parameters with regard
to the particular motor type and inverter type combination.
Adapt software parameters if necessary.
U
-
f
f
U
f
T
n
T
o
T
L
T
T
-
-
-
Quick Start Guide ANG
V
Maximum input voltage, three-phase
eff.
-
Short circuit / earth fault proof
Hz
0 ... 599, depending on switching frequency
kHz
V
Hz
°C
0 ... 40 (3K3 DIN IEC 60721-3-3)
0...55°C, as from 40°C, power reduction of
°C
2.5% / K should be considered
°C
°C
%
15 ... 85; not condensing
-
-
2, 4, 8, 16
320 ... 528
45 ... 66
-25 ... 55
-25 ... 70
vertical
IP20 (EN60529)
07/20