Descargar Imprimir esta página

Toshiba Carrier MCY-MAP0367HS-UL Manual De Instalación página 8

Publicidad

Idiomas disponibles

Idiomas disponibles

• As shown in the figure below, install vibration-proof rubber pads to directly support the bottom surface of the fixing leg.
* When installing the foundation for an outdoor unit with downward piping, consider the piping work.
Correct
Fixing leg
Foundation
Incorrect
If only the end of the
fixing leg is supported,
it may deform.
Foundation
Set the out margin of the anchor bolt to 0.6" (15 mm) or less .
• When the unit is to be installed in a location where it is likely to be exposed to strong winds or where the foundation
is unstable, additional measures must be taken to prevent tip-over as shown in the figure below.
Tip-over prevention brace
CAUTION
• Carry out the installation work by following the prescribed procedure to help prevent the unit from shaking in the
event of strong winds, earthquakes, etc.
• Failure to carry out the installation work as prescribed may lead to the unit tipping over, in turn causing an accident.
 For reference
Attach a snow stand, snow hood, etc. to the outdoor unit for use in snowfall areas.
It is recommended to procure an anti-freeze heater locally to safely install the air conditioner.
For details, contact the dealer.
EN-13
Correct
Absorb vibration with
Bottom plate of
vibration-proof rubber
outdoor unit
pads
Foundation
Support the bottom surface of the
fixing leg that is in contact with and
underneath the bottom plate of the
outdoor unit.
Do not support the outdoor
unit only with the fixing leg.
0.6" (15 mm) or less
Tip-over prevention brace
– 7 –
5
Refrigerant Piping
 Leading out the pipes
• The indoor/outdoor unit connecting pipes can be connected in any of 3 directions. Use a screwdriver to punch out
the knockout part of the piping/wiring panel or base. Wear heavy work gloves to protect yourself from injury while
doing this work. After punching out the knockout hole in a manner which ensures that the pipes and wires will not be
damaged in any way, remove the burrs from around the hole. Use the protective edge guard around the opening.
 Optional installation parts (field supplied)
Part name
Refrigerant piping
A
Liquid side: Ø3/8" (Ø9.52 mm)
Gas side: Ø5/8" (Ø15.88 mm) or Ø3/4" (Ø19.05 mm)
Pipe insulating material
B
(polyethylene foam, 0.4" (10 mm) thick)
C
Putty, PVC tape
REQUIREMENT
Follow the instructions in the installation manual provided with the branch pipe kit and the instructions in the indoor
unit's installation manual to connect the refrigerant pipe between the branch pipe and indoor unit.
Rear
Side
Bottom
Quantity
One each
1
One each
EN-14

Publicidad

loading

Este manual también es adecuado para:

Mcy-map0487hs-ulMcy-map0607hs-ul