18 EN – Quick installation and start-up guide
Connection
XDI Digital inputs
EN
DA
X12
X13
DE
X205
ES
The wire size accepted by all screw terminals (for both stranded and solid wire) is 0.5
FI
2
... 2.5 mm
(24...12 AWG). The torque is 0.5 N·m (5 lbf·in).
FR
Remove the cardboard covers
IT
After the electrical installation has been done and there is no danger of dropping
screws or anything else inside the drive or LCL filter module, remove the cardboard
NL
covers from the top of them. See
covers (page
290).
PL
Start-up the drive
PT
SV
Before you start up the drive, make sure that the installation is completed.
Make sure also that it is safe to start the motor. Disconnect the motor from
TR
other machinery if there is a risk of damage or injury.
ZH
Before you activate the automatic fault reset or automatic restart functions
of the drive control program, make sure that no dangerous situations can
occur. These functions reset the drive automatically and continue operation
after a fault or supply break. If these functions are activated, the installation
must be clearly marked as defined in IEC/EN/UL 61800-5-1, subclause 6.5.3,
for example, "THIS MACHINE STARTS AUTOMATICALLY".
Use the control panel to do the start-up procedure. The two commands at the bottom
of the display show the functions of the two softkeys
display. The commands assigned to the softkeys are different depending on the
context. Use the arrow keys
depending on the active view. Key
Term
DI1
+24VD
DI2
1
DI1
DI3
2
DI2
DI4
3
DI3
DI5
4
DI4
DI6
5
DI5
6
DI6
Safe torque off circuits must be closed for the drive to start.
XSTO
Safety options connection
Control panel connection
Memory unit connection
Installing the air baffles and removing the cardboard
,
,
and
?
shows a context-sensitive help page.
Description
Stop (0) / Start (1)
Forward (0) / Reverse (1)
Reset
Acc/Dec time select
Constant speed 1 (1 = On)
By default, not in use.
and
located below the
to move the cursor or change values