Operating Instructions
CAUTION!
X.TUNE ERROR 5!
If the message X.TUNE ERROR 5 is displayed after starting the X.TUNE function, the alignment of the RPC positioner type shaft to the
actuator shaft is not correct.
► Check alignment (as described in this chapter).
► Then repeat the X.TUNE function.
CAUTION!
Do not apply pressure to the positioner during assembly!
Unpredictable actuation may result in injury or property damage.
► When assembling the positioner to actuator, the control air connections must not be connected.
CAUTION!
Incorrect adapter size!
To avoid material damage, the components must be compatible.
► The type RPC positioner must be compatible with valve (type and dimension), as well as the attachments.
NOTE!
When assembling on process valve with rotary actuator, the assembly instructions in the operating manual of the process valve
must also be observed.
4.4
Pneumatic installation
5
9
10
CAUTION!
Damage or functional failure due to incorrect connection!
An incorrect pneumatic connection can damage the type RPC positioner. Prevent ingress of dirt and moisture with any open connec-
tions.
► Before putting into operation, ensure correct pneumatic connection according to the diagram.
► Perform a function test upon putting into operation.
► To maintain the IP65/IP67 protection rating, connect the control air outlet that is not required to the free control air connection
of the actuator or close it with a sealing plug.
8
7
6
No.
Designation
1
Valve
2
Actuator
4
3
Assembly bridge
4
Type RPC Positioner
5
Fixing screws
6
Control air connection A1
3
7
Pressure connection P
8
Control air connection A2
9
Control air connection
2
Connection
10
Control air connection
Actuator
1
Type RPC D/PID positioner
19