Type RPC D/PID positioner
7.2.3
Manually changing the process setpoint value
1. Setting the internal setpoint
2. Change process setpoint value manually
1
Return without change
2
Increase figure
3
Move one position to the left;
4
Apply set value
5
Changeable number
42
MENU
Press for 3 s. Change from process level to setting level.
P.CONTROL
selection. Selection in the main menu (MAIN).
ENTER
selection. The sub-menu items for the basic setting are displayed.
SETUP
selection.
ENTER
selection. The menu for setting up the process controller is displayed.
SR-INPUT
selection.
ENTER
selection. The sub-menu items for the basic setting are displayed.
internal
selection.
ENTER
selection. The menu item has been activated.
4x EXIT
selection. Return to process level.
30.0
SP
SP
m3/min
MENU
PV
PV (t) INPUT
INPUT
SET VALUE
SP:
070.0
[m3/min]
+
+
<-
ESC
1
2
3
Use the arrow buttons to select the display for the process
setpoint value (SP).
Press the INPUT button.
Enter process setpoint value
70.0
5
OK
4