Engine And Alternator; Column; Cleaning; Greasing The Pulleys - SDMO RL6-1b Manual De Uso Y Mantenimiento

Tabla de contenido

Publicidad

The refrigerant level should only be checked with the engine cold.
Important
The coolant level can be checked visually via the access flap (no. 1) by opening it and then opening the radiator cap.
Top up the oil if necessary.
Close the radiator cap and then the access flap.
1

9.2. Engine and alternator

The maintenance procedures for the engine and alternator fitted on the generating set are described in appendices B and C.

9.3. Column

9.3.1 Cleaning

Regular cleaning of the machine is recommended in order to prevent any deposits of dirt that could compromise its efficiency. The
frequency of this operation depends on its place of use.

9.3.2 Greasing the pulleys

To lubricate the pulleys (figure 9.1), use the grease recommended for low temperature and very high speed applications. It is
recommended to use SKF LGLT 2 grease, a top quality lithium soap product with a 100 % synthetic base oil. If using another lubricant,
this must still be characterised by a base oil viscosity of 18 mm²/s at 40°C and 4.5 mm²/s at 100°C.
Figure 9.1 – Pulley greasing
72/372

Publicidad

Tabla de contenido
loading

Tabla de contenido