AVENTICS | EtherNet/IP™ | R412012728–BDL–001–AC
7.3.2

Configuring inputs and outputs

The inputs and outputs can be configured as shown in the following example.
1. In the program RSLogix5000, double click the branch "Controller Tags" under
"Controller Logix5561" in the tree structure.
Different menu groups appear in the right area of the window. The menu group
with the name stored in the configuration (in the example "BDesign") represents
the valve unit B-Design EthernetIP.
2. Expand the menu group "BDesign:O" by clicking the "+" symbol.
3. Expand the menu group "BDesign:O Data" by clicking the "+" symbol.
The following window appears:
Fig. 13:
Controller Tags window area
As soon as you expand the listed bytes (e.g. "BDesign:O.Data[0]") by clicking the
"+" symbol, the corresponding bits are displayed.
You can view input and diagnostic data by expanding the menu group "BDesign:I".
Example:
BDesign:I.Data[6] (Module Diagnostics)
Bit
Function
0
none <value = 0>
1
none <value = 0>
2
Supply voltage for outputs 1-8
3
Supply voltage for outputs 9-16
4
Supply voltage for outputs 17-32
5
Electrical supply voltage for external modules
6
none <value = 0>
7
none <value = 0>
Commissioning and Operation
67