Commissioning and operation
Table 19:
Setting options for switch S8
Switch
Bus
setting S8
terminator
OFF
Off
ON
On
7.1.5

Setting the bus terminator

In order to minimize line reflections and to ensure a defined rest
level on the CANopen transfer line, a bus terminator has to be
fitted on both ends of the transfer line.
In the bus coupler, the bus terminator has been integrated into
the device and can be defined using switch S8.
Fig. 10: Switch S8 for bus terminator
The bus terminator setting is located beneath the PG fitting B
(see Fig. 10).
Set the bus terminator with switch S8 (see Tab. 19).
O
Outgoing bus on
X72 (BUS OUT)
On
Off
The switch is in the OFF position when delivered, i.e. the bus
terminator is switched off.
7.2

Configuring the bus system

The settings to be made for the overall system during the bus
configuration are superior to the already described settings on
the bus coupler.
X71
A
X72
B
X10
Application
When the bus coupler is connected to another module
and does not form the end of the transfer line.
When the bus coupler is positioned at the end of the
transfer line.
ON
OF F
S8
U
Q1
U
Q2
S4 S5 S6