Total current is too high
Every output is supplied with a continuous current of max.
0.5 A. Current loads over 0.5 A per output can lead to limited
system functioning.
O
Make sure that the current load of 0.5 A per output is not
exceeded.
6.3.4

Connecting the output module load supply

Each output module has its own M12 connection for the load
supply. Each of the 4 outputs are supplied via the load supply.
The U
and U
voltages are galvanically isolated.
Q1
Q2
The connection cable for the output module load supply must
meet the following requirements:
W
Cable socket: M12x1, 4-pin, A-coded without center hole
(to ensure correct plug-in connection)
Cable cross section: 0.5 mm
W
W
Length: Max. 20 m
1. Set up the correct pin assignment (see Tab. 11) on the plug
connections if you do not use pre-assembled wiring.
2. Connect the load supply using the M12 plug.
Table 11:
Load supply assignment for 8x output module, DO8, M12x1,
A-coded
Pin
X10
Assignment
1
0V_U
GND reference for power supply 2
Q2
2
24V_U
24 V supply voltage 1 for outputs O0 to O3
Q1
3
0V_U
GND reference for power supply 1
Q1
4
24V_U
24 V supply voltage 2 for outputs O4 to O7
Q2
NOTICE
2
per wire
83