Descargar Imprimir esta página

YASKAWA LA500 Manual De Instrucciones página 18

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 138
1 English
Environment
Storage
-20 °C to +70 °C (-4 °F to +158 °F) (short-term temperature during transportation)
Temperature
Pollution degree 2 or less
Install the drive in an area without:
• Oil mist, corrosive or flammable gas, or dust
• Metal powder, oil, water, or other unwanted materials
• Radioactive or flammable materials.
Surrounding Area
• Harmful gas or fluids
• Salt
• Direct sunlight
Keep wood and other flammable materials away from the drive.
1000 m (3281 ft) Maximum
Altitude
• 10 Hz to 20 Hz: 1 G (9.8 m/s
Vibration
• 20 Hz to 55 Hz: 0.6 G (5.9 m/s
Installation
Install the drive vertically for sufficient airflow to cool the drive.
Orientation
Removing/Reattaching Covers
DANGER
drive. Before servicing, disconnect all power to the equipment and wait for the time specified on the warning label
at a minimum. The internal capacitor stays charged after the drive is de-energized. The charge indicator LED
extinguishes when the DC bus voltage decreases below 50 Vdc. When all indicators are OFF, measure for
dangerous voltages to make sure that the drive is safe. If you do work on the drive when it is energized, it will
cause serious injury or death from electrical shock.
Electrical Installation
DANGER
drive. Before servicing, disconnect all power to the equipment and wait for the time specified on the warning label
at a minimum. The internal capacitor stays charged after the drive is de-energized. The charge indicator LED
extinguishes when the DC bus voltage decreases below 50 Vdc. When all indicators are OFF, measure for
dangerous voltages to make sure that the drive is safe. If you do work on the drive when it is energized, it will
cause serious injury or death from electrical shock.
WARNING
Charge LED turns off. Remove the front cover and terminal cover to do work on wiring, circuit boards, and other
parts. Use terminals for their correct function only. Incorrect wiring, incorrect ground connections, and incorrect
repair of protective covers can cause death or serious injury.
WARNING
switch. If you touch electrical equipment that is not grounded, it can cause serious injury or death.
WARNING
Refer to the technical manual for more information about the I/O terminals. Wiring and grounding incorrectly or
modifying the cover may damage the equipment or cause injury.
18
Note:
Derate the output current by 1% for each 100 m (328 ft) to install the drive in altitudes between
1000 m to 4000 m (3281 ft to 13123 ft).
It is not necessary to derate the rated voltage in these conditions:
• Installing the drive at 2000 m (6562 ft) or lower
• Installing the drive between 2000 m to 4000 m (6562 ft to 13123 ft) and grounding the neutral
point on the power supply.
Contact Yaskawa or your nearest sales representative when not grounding the neutral point.
Electrical Shock Hazard. Do not examine, connect, or disconnect wiring on an energized
Electrical Shock Hazard. Do not examine, connect, or disconnect wiring on an energized
Electrical Shock Hazard. De-energize the drive and wait 5 minutes minimum until the
Electrical Shock Hazard. Correctly ground the drive before you turn on the EMC filter
Electrical Shock Hazard. Use the terminals for the drive only for their intended purpose.
Conditions
2
, 32.15 ft/s
2
)
2
2
, 19.36 ft/s
)
YASKAWA TOMPYEULA5001C LA500 Installation and Operation Instructions

Publicidad

loading