Descargar Imprimir esta página

YASKAWA LA500 Manual De Instrucciones página 270

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 138
9 Attachment
Model
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4045
-, +1, +2
B1, B2
*1
Remove insulation from the ends of wires to expose the length of wire shown.
*2
If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use the closed-
loop crimp terminals to connect a protective ground wire that has a minimum cross-sectional area of 10 mm
(copper wire).
270
Recomm.
Applicable
Gauge
Gauge
2
2
mm
mm
25
6 - 35
16
4 - 25
25
6 - 35
10
2.5 - 16
10
6 - 16
YASKAWA TOMPYEULA5001C LA500 Installation and Operation Instructions
Wire
Terminal Screw
Stripping
Length
*1
Size
Shape
mm
18
M5
18
M5
18
M5
10
M4
-
M6
Tightening
Torque
N∙m (in∙lb)
• ≤ 25 mm
2
2.3 - 2.5
(19.8 - 22)
• 35 mm
2
4.1 - 4.5
(36 - 40)
2.3 - 2.5
(19.8 - 22)
• ≤ 25 mm
2
2.3 - 2.5
(19.8 - 22)
• 35 mm
2
4.1 - 4.5
(36 - 40)
1.5 - 1.7
(13.5 - 15)
5.4 - 6.0
(47.8 - 53.1)
2

Publicidad