Maintenance
7
7.3
Opening the burner
Disconnect the electrical supply from the burner.
Loosen the screws 1) and remove the hood 2).
Disengage the articulated coupling 7) from the graduated
sector 8).
Assemble the two extensions on the sliding bars 4).
Remove the screws 3) and move the burner backwards
some 100 mm on the guides 4). Disconnect the probe and
electrode leads and then pull the burner fully back.
Now extract the gas distributor 5) after having removed the
screw 6).
20032905
4
2
D8698
26
7.4
Closing the burner
Push the burner up to approximately 100 mm from the
pipe coupling.
Reconnect the cables and slide the burner as far as the
stop.
Replace the screws 3) and carefully pull the probe and
electrode cables outwards until they are slightly taut.
Re-couple the articulated coupling 7) to the graduated
sector 8).
Disassemble the two extensions from the guides 4).
6
7
3
1
GB
8
5
1
Fig. 38