Descargar Imprimir esta página

Beninca BEVA.5 Manual De Instrucciones página 24

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 47
12.2) PROGRAMMING
The programming of the various functions of the control unit is carried out using the LCD display on the control unit and setting the
desired values in the programming menus described below.
The parameters menu allows you to assign a numerical value to a function, in the same way as a regulating trimmer.
The logic menu allows you to activate or deactivate a function, in the same way as setting a dip-switch.
12.2.1) TO ACCESS PROGRAMMING
1 -Press the <PG> button to enter the first Installation menu "INST".
2 -Choose with <+> or <-> button the menu you want to select (see menu at page 10-11)
3 - Press the button <PG>, the display shows the first function available on the menu.
4 - With the <+> or <-> button, select the function you want.
5 - Press the button <PG>, the display shows the value currently set for the function selected.
6 - With the <+> or <-> button, select the value you intend to assign to the function.
7 - Press the button <PG>, the display shows the signal "PRG" which indicates that programming has been completed.
12.2.2) PROGRAMMING NOTES
Simultaneously pressing <+> and <-> from inside a function menu allows you to return to the previous menu without making any changes.
Hold down the <+> key or the <-> key to accelerate the increase/decrease of the values.
Hold down the <+> key or the <-> key to accelerate the increase/decrease of the values.
After waiting 120s the control unit quits programming mode and switches off the display.
When the board is switched on, the software version is displayed for around 5 sec
The pre-set logic functions and parameters are made taking account of a typical installation.
12.2.3) QUICK PROGRAMMING
-Enter the INST menu
-Verify that the parameter BOOM is correct: 3-5 for EVA.5, 7-8 for EVA.7
-Set the barrier position by means of the menu POS, by default the barrier is set as RIGHT BARRIER
-Enter the menu AUTO, confirm with <PG> and wait until the barrier has carried out the autoset of the parameters
-By means of the menus PAR and LOG, select the parameters and the logic functions wanted according to the type of installation in object
-IMPORTANT: After every change of the parameters FSTS. SLDO, SLDC, TSMO, TSMC, the barrier executes an opening maneuver fol-
lowed by a closing one in order to acquire the new values of current and torque, on the screen will appear the message <PRG>
12.3) PARAMETERS, LOGICS AND SPECIAL FUNCTIONS
The following tables describe the functions available on the control unit
MENU
Select the length of the boom installed on the barrier.
BOOM
Value expressed in meter from 3m to 5m (EVA5) or from 7m to 8m (EVA7)
According to the selected boom length, the optimal value of speed will be set.
Set the closing direction of the barrier (see fig. 2)
The symbol 0--- indicates right barrier (R/RIGHT) DEFAULT
Pos
The symbol ---0 indicates left barrier (L/LEFT)
Verify the opening direction of the boom and in case reverse it. Every change of
this function automatically implies the starting of a new AUTOSET procedure.
MENU
Automatic closing time. Enabled only with logic "TCA"=ON.
TCA
At the end of the set time, the control unit commands a closing maneuver .
Adjusts the opening and closing speed of the barrier (standard speed, before the
FSTS
slowdown phase).
Adjusts the slowdown speed of the barrier during the opening phase* (Fig.11 -slow
sldo
Open).
Adjusts the slowdown speed of the barrier during the closing phase * (Fig.12 -slow
sldc
Close).
Sets the starting point of the slowdown during the opening phase (Fig.11- beginning
tsmo
of the slow Open). The value is expressed in percentage on the entire stroke.
Sets the starting point of the slowdown during the closing phase (Fig.12- beginning of
tsmc
the slow Close). The value is expressed in percentage on the entire stroke.
PMO
Adjusts the motor torque applied to the barrier during the opening phase.*
PMC
Adjusts the motor torque applied to the barrier during the closing phase.*
Adjusts the motor torque applied to the barrier during the slowdown in opening phase
PSO
* (Fig.10 - Slow Open).
Adjusts the motor torque applied to the barrier during the slowdown in closing phase
PSC
* (Fig.11 - Slow Close).
24
INSTALLATION (inst)
FUNCTION
PARAMETERS (PAR)
FUNCTION
MEMO
MIN-MAX-(Default)
3/5 -7/8 (3-5)
= RIGHT
0---
= LEFT
---0
( RIGHT )
MEMO
MIN-MAX-(Default)
1-240-(20s)
50-99-(99)
20-70-(50)
20-70-(50)
1-99-(20)
1-99-(20)
1-99-(20)
1-99-(20)
1-99-(20)
1-99-(20)

Publicidad

loading

Este manual también es adecuado para:

Eva.5