7 Configuration
[2-32]
Forced, all time, power consumption limitation operation (no external
control adaptor is required to perform power consumption limitation).
If the system always needs to be running under power consumption
limitation conditions, this setting activates and defines the level
power consumption limitation that will be applied continuously. The
level is according to the table.
[2-32]
0 (default)
Function not active.
1
Follows [2-30] setting.
2
Follows [2-31] setting.
[2-50]
Antifreeze type setting.
By changing this setting, you can extend the operation range at the
antifreeze side of the unit.
▪ Normal operation range at antifreeze side (default): for use with
water as heat source medium.
▪ Extended operation range at antifreeze side (default): for use with
antifreeze as heat source medium.
NOTE
By changing this setting to extended operation type,
propylene glycol or ethylene glycol must be used as heat
source medium to avoid freeze up of the antifreeze circuit
or unit itself (cf. operation range). Do not use water in this
case!
[2-50]
0 (default)
Water
2
EG 35%
3
EG 45%
4
EG 30%, PG 30%
5
PG 35%
6
EG 40%, PG 40%
7
PG 45%
8
EG 50%, PG 50%
9
EG 10%, PG 10%
10
EG 15%, PG 15%
11
EG 20%, PG 20%
12
EG 25%, PG 25%
EG: Ethylene Glycol (wt%)
PG: Propylene Glycol (wt%)
[2-73]
Heat rejection cancellation control setting.
[2-73]
0 (default)
OFF
1
ON (with priority on cooling capacity)
2
ON (with priority on heat rejection cancellation)
Heat rejection cancellation control can be OFF if the mechanical
room is already equipped with a ventilation system or air
conditioning system for other facilities.
[2-74]
Heat rejection cancellation setting temperature.
If the unit internal temperature is higher than the zero energy
dissipation setting temperature, the zero energy dissipation control
will start and cool down the unit.
Installation manual
38
Restriction reference
Description
Description
[2-74]
0
77°F (25°C)
1
80.6°F (27°C)
2
84.2°F (29°C)
3 (default)
87.8°F (31°C)
4
91.4°F (33°C)
5
95°F (35°C)
6
98.6°F (37°C)
7
102.2°F (39°C)
[2-81]
Cooling comfort setting.
This setting is used in conjunction with setting [2-8].
[2-81]
0
Eco
1 (default)
Mild
2
Quick
3
Powerful
[2-82]
Heating comfort setting.
This setting is used in conjunction with setting [2-9].
[2-82]
0
Eco
1 (default)
Mild
2
Quick
3
Powerful
7 .2 .9
To connect the PC configurator to the
outside unit
2
3
4
5
a
PC
b
Cable (999482P3)
c
Outside unit main PCB
RWEQ96~432TATJU + RWEQ96~432TAYDU
VRV W T-Series water-cooled system air conditioner
Description
Cooling comfort setting
Heating comfort setting
a
c
b
X27A
A1P
4P484115-1A – 2017.10