5 .8 .3

About the electrical wiring

It is important to keep the power supply and the transmission wiring
separated from each other. In order to avoid any electrical
interference the distance between both wiring should always be at
least 1 inch.
NOTE
▪ Be sure to keep the power line and transmission line
apart from each other. Transmission wiring and power
supply wiring may cross, but may not run parallel.
▪ Transmission wiring and power supply wiring may not
touch internal piping (except the inverter PCB cooling
pipe) in order to avoid wire damage due to high
temperature piping.
▪ Firmly close the lid and arrange the electrical wires so
as to prevent the lid or other parts from coming loose.
The transmission wiring outside the unit should be routed in conduit.
Be sure to follow the limits below. If the unit-to-unit cables are
beyond these limits, it may result in malfunction of transmission:
Description
Maximum wiring length
Total wiring length
Maximum inter unit wiring length between
outside units
Transmission wiring to cool/heat selector
Maximum number of branches for unit-to-
unit cabling
(a)
Maximum number of independent
interconnectable systems
(a)
No branching is allowed after branching (see figure below).
In case of heat recovery mode
A
B
a
a
a
b
b
a
Outside unit
b
Indoor unit
c
Main line
d
Branch line 1
e
Branch line 2
f
Branch line 3
g
No branch is allowed after branch
h
Central user interface (etc...)
A
Outside/indoor transmission wiring
B
Main/sub transmission wiring
RWEQ96~432TATJU + RWEQ96~432TAYDU
VRV W T-Series water-cooled system air conditioner
4P484115-1A – 2017.10
Limitation
3280 ft
6560 ft
98 ft
1640 ft
16
10
h
d
b
e
b
g
b
f
g
b
c
In case of heat pump mode
A
B
a
a
a
b
b
a
Outside unit
b
Indoor unit + Branch selector unit
c
Main line
d
Branch line 1
e
Branch line 2
f
Branch line 3
g
No branch is allowed after branch
h
Central user interface (etc...)
A
Outside/indoor transmission wiring
B
Main/sub transmission wiring
For the above wiring, always use vinyl cords with AWG18 to AWG16
sheath or cables (2-core wires). 3-core wire cables are only
allowable for the cooler/heater changeover user interface.
5 .8 .4

To route and fix the transmission wiring

Transmission wiring can be routed through the front side only. Fix it
to the upper mounting hole.
A
Fix to the indicated plastic brackets (factory installed).
5 Installation
h
d
b
e
b
g
b
f
g
b
c
A
TO IN/D UNIT TO OUT/D UNIT TO MULTI UNIT
F1
F2
F1
F2 Q1 Q2
A1P
Installation manual
31

Publicidad

Tabla de contenido