Combining units and options

3 .5 .1

About combining units and options

NOTE
Refer to the technical engineering data for latest options
and allowable combinations.
The VRV W T-Series water-cooled system can be combined with
several types of indoor units and is intended for R410A use only.
For an overview which units are available you can consult the
product catalogue for VRV W T-Series water-cooled system.
An overview is given indicating the allowed combinations of indoor
units and outside units. Not all combinations are allowed. They are
subject to rules (combination between outside-indoor, single module
use, multiple module use, combinations between indoor units, etc.)
mentioned in the technical engineering data.
3 .5 .2

Connection Ratio

Connection Ratio = Total capacity index of the indoor units /
Capacity index of the outside units
Type
Types of connected outside units
Single outside units
Double outside units
Triple outside units
Types of connected indoor units
When using
Type
only FXDQ,
FXMQ-P,
FXAQ,
FXSQ07~54T
Single outside units
150% (*1)
Double outside units
Triple outside units
150% (*1)
*1. If the operational capacity of indoor units is more than 130%, low
airflow operation is enforced in all the indoor units.
*2. 120% for RWEQ432TATJU/TAYDN
Installation manual
8
f
g
Min . connection ratio
RWEQ-T type
50%
Max . connection ratio
When using at
least one
All other
FXFQ07/09,
models
FXZQ05T,
FXSQ05T
150% (*1)
150% (*1)
130%
130%
130% (*2)
130% (*2)
3 .5 .3

Possible combinations of outside units

Possible single module units
RWEQ96
RWEQ120
RWEQ144
Possible standard combinations of units
RWEQ192~432 consists of 2 or 3 RWEQ96~144 units.
RWEQ192 = RWEQ96 + 96
RWEQ216 = RWEQ120 + 96
RWEQ240 = RWEQ120 + 120
RWEQ264 = RWEQ120 + 144
RWEQ288 = RWEQ144 + 144
RWEQ312 = RWEQ120 + 96 + 96
RWEQ336 = RWEQ120 + 120 + 96
RWEQ360 = RWEQ120 + 120 + 120
RWEQ384 = RWEQ144 + 120 + 120
RWEQ408 = RWEQ144 + 144 + 120
RWEQ432 = RWEQ144 + 144 + 144
3 .5 .4

Outside Unit Combinations

Total capacity of indoor units needs to be within the specified range.
<Outside unit>
<Total capacity index of indoor units>
RWEQ96TATJU/TAYDU
............................ 48-124
RWEQ120TATJU/TAYDU ............................ 60-156
RWEQ144TATJU/TAYDU ............................ 72-187
RWEQ192TATJU/TAYDU ............................ 96-249
RWEQ216TATJU/TAYDU ........................... 108-280
RWEQ240TATJU/TAYDU ........................... 120-312
RWEQ264TATJU/TAYDU ........................... 132-343
RWEQ288TATJU/TAYDU ........................... 144-374
RWEQ312TATJU/TAYDU ........................... 156-405
RWEQ336TATJU/TAYDU ........................... 168-436
RWEQ360TATJU/TAYDU ........................... 180-468
RWEQ384TATJU/TAYDU ........................... 192-499
RWEQ408TATJU/TAYDU ........................... 204-530
RWEQ432TATJU/TAYDU ........................... 216-561
NOTE
Higher capacity than the above table can be selected, this
may affect heating and cooling capacity. For additional
information see technical engineering data.
RWEQ96~432TATJU + RWEQ96~432TAYDU
VRV W T-Series water-cooled system air conditioner
4P484115-1A – 2017.10