Method For Removing Shipping Plate; Identification And System Layout; Standard Operation Limit - Daikin VRV W T Serie Manual De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3 Identification and system layout

Accessory pipes
MBH
(inch)
Gas pipe
96
120
▪ Front connection
(a)
Øa
144
Øb
▪ Top connection
Øc
Ød
Accessory pipes
MBH
(inch)
High pressure/Low
96
pressure gas pipe
120
▪ Front connection
(a)
144
Øa
Øb
▪ Top connection
Øc
Ød
(a)
Braze the straight accessory pipe onto the L-shaped
accessory pipe in order to get the correct diameter to
connect the field pipes (for front connection).
2 .4
Method for removing shipping
plate
NOTE
If the unit is operated with the transportation stay attached,
abnormal vibration or noise may be generated.
The compressor transportation stay must be removed. It is installed
under the compressor leg in order to protect the unit during
transport. Proceed as shown in the figure and procedure below.
1 Remove the bolt.
2 Lift the insulation to access the compressor mounting bolt.
3 Slightly loosen the mounting bolt.
4 Remove the transportation stay as shown in the figure below.
5 Tighten the mounting bolt to 9.07 lbf·ft of torque.
2
1
Installation manual
6
Øa
Øb
Øc
Ød
1
1
1
7/8
1-1/8
Øa
Øb
Øc
Ød
1
1
1
3/4
7/8
5
(9.1 lbf·ft)
3
2
3
Identification and system
layout
3 .1

Standard operation limit

The figures below assume following operating conditions for indoor
and outside units:
Equivalent pipe length ......................................... 25 ft (7.6 m)
Level difference..................................................................... 0
Cooling
A
120
110
100
90
80
70
60
50
50
60
70
80
90
B
<In case of antifreeze usage>
Cooling
A
120
110
100
90
80
70
60
50
40
30
20
50
60
70
80
90
B
A
Entering water temperature (°F)
B
Indoor temperature (°FWB)
C
Indoor temperature (°FDB)
Range for continuous operation
Range for operation
Range for pull down operation
Range for warming up operation
▪ Operation range of water flow rate is 13 .2-39 .6 gpm (50-150 L/min).
(21.2-39.6 gpm (80-150 L/min) in case of antifreeze usage.)
• The unit is designed for the following operation range;
Entering water temperature: 67-95°F (20-35°C)
Relative humidity below 80%
Water flow rate: 15 .9 gpm (60 L/min) or more
• During cooling operation when the outside temperature is very
low, it is possible that the thermostat switches off automatically in
order to protect the unit from freezing.
• Hold ambient temperature at 35-104°FDB (2-40°CDB).
Heat release from the unit (approx.): RWEQ96: 2730 Btu/h (0.8 kW),
RWEQ120: 3412 Btu/h (1.0 kW), RWEQ144: 4436 Btu/h (1.3 kW)
There is no heat release from the unit if the heat rejection
cancellation is activated.
It is recommended to always ventilate the room if this function is not
activated.
RWEQ96~432TATJU + RWEQ96~432TAYDU
VRV W T-Series water-cooled system air conditioner
Heating
A
120
110
100
90
80
70
60
50
50
60
70
80
90
C
Heating
A
110
100
90
80
70
60
50
40
30
20
10
50
60
70
80
90
C
4P484115-1A – 2017.10