5 Installation
5 .8 .5

To connect the transmission wiring

The wiring from the indoor units must be connected to the F1/F2
(In-Out) terminals on the PCB in the outside unit.
Tightening torque for the transmission wiring terminal screws:
Screw size
M3.5 (A1P)
In case of heat recovery mode
TO IN/D UNIT TO OUT/D UNIT TO MULTI UNIT
d
F1
F2
F1
F2 Q1Q2
a
b
A1P
A1P
F
F
F
F
Q
Q
Q
Q
1
2
1
2
1
2
1
2
e
e
g
a
Unit A (main outside unit)
b
Unit B (sub outside unit)
c
Unit C (sub outside unit)
d
Outside unit PCB (A1P)
e
Main/sub transmission (Q1/Q2)
f
Outside/indoor transmission (F1/F2)
g
Outside unit/other system transmission (F1/F2)
h
Branch selector unit
i
Indoor unit
j
Cooling-only VRV indoor unit
In case of heat pump mode
b
c
d
A1P
F1 F2 F1 F2 Q1 Q2
Q1 Q2
Q1 Q2
e
f
f
e
F1 F2
F1 F2
h
i
F1 F2
F1 F2
a
Outside unit PCB (A1P)
b
Unit A (main outside unit)
c
Unit B (sub outside unit)
d
Unit C (sub outside unit)
e
Outside unit/other system transmission (F1/F2)
f
Outside-outside unit transmission (Q1/Q2)
g
Indoor unit
h
Use the conductor of sheathed wire (2 wire) (no polarity)
i
Terminal board (field supply)
▪ The interconnecting wiring between the outside units in the same
piping system must be connected to the Q1/Q2 (Out Multi)
terminals. Connecting the wires to the F1/F2 terminals results in
system malfunction.
▪ The wiring for the other systems must be connected to the F1/F2
(Out-Out) terminals of the PCB in the outside unit to which the
interconnecting wiring for the indoor units is connected.
▪ The base unit is the outside unit to which the interconnecting
wiring for the indoor units is connected.
Installation manual
32
Tightening torque (lbf·ft)
0.59~0.7
f
F1 F2 F1 F2
F1 F2 F1 F2
TO IN/D
TO OUT/D
TO IN/D
TO OUT/D
UNIT
UNIT
UNIT
UNIT
h
h
c
A1P
Q
Q
1
2
F1 F2
F1 F2
F1 F2
F1 F2
i
i
j
F1 F2
F1 F2
F1
F2
F1
F2 Q1 Q2
TO IN/D UNIT TO OUT/D UNIT TO MULTI UNIT
g
a
F1 F2
F1 F2
5 .8 .6

To finish the transmission wiring

After installing the transmission wires inside the unit, wrap them
along with the on-site refrigerant pipes using finishing tape, as
shown in figure below.
c
f
b
d
f
a
e
f
a
Liquid pipe
b
Gas pipe
c
Finishing tape
d
High pressure/low pressure gas pipe
e
Transmission wiring (F1/F2)
f
Insulator
5 .8 .7

To route and fix the power supply

NOTE
When routing ground wires, secure clearance of 1 inch or
more away from compressor lead wires. Failure to observe
this instruction properly may adversely affect correct
operation of other units connected to the same ground.
The power supply wiring can be routed from the front side. Exit the
wiring via the upper mounting hole.
5 .8 .8

To connect the power supply

NOTE
Never connect the power supply to transmission wiring
terminal block. Otherwise the entire system may break
down.
RWEQ96~432TATJU + RWEQ96~432TAYDU
VRV W T-Series water-cooled system air conditioner
A1P
4P484115-1A – 2017.10