6 Checking of device and installation conditions

NOTE
In case of two or more flow switches installed with field
setting [2-24-3] activated (see "7.2.8 Mode 2: Field setting"
on page
36), be sure to use the flow switch that close the
contact in 5 seconds after the water pump operation
request signal turned on.
Failure to do so will result in malfunction.
Example:
1 2 3 4 5 6 7 8 9 10
+
10
Y
X3M
X2M
X
Relay (close contact when no compressor operation signal)
(field supply)
Y
Flow switch (open contact when no flow signal) (field
supply)
Multifunction outputs
To monitor the outside unit operation or trigger field supplied
equipment connected to the outside unit, this RWEQ*T, series is
equipped with 5 output contacts.
General contact specifications: 220 V AC, 3 mA-0.5 A.
To connect these output signals, choose the applicable contacts in
the X3M terminal in the table below:
X3M
a
b
c
d
X3M
e
Terminal
Function
a
Error on remote controller
b
Compressor operation
c
Heating operation
d
Cooling operation
e
Valve/Pump operation request
6
Checking of device and
installation conditions
Be sure to check the followings.
For those doing electrical work
1 Make sure there is no faulty transmission wiring or loosening of
a nut.
See
"5.8.5 To connect the transmission wiring" on page
Installation manual
34
X2M
-
0
TW1
TW2
IN
OUT
X3M
X
YLW
a
ORG
RED
b
BRN
BLU
c
BLU
WHT
d
WHT
BLK
e
BLK
1
YLW
2
ORG
RED
3
4
BRN
5
BLU
BLU
6
7
WHT
8
WHT
9
BLK
10
BLK
32.
2 Make sure there is no faulty power wiring or loosening of a nut.
See
"5.8.8 To connect the power supply" on page
3 Has the insulation of the main power circuit deteriorated?
Measure the insulation and check the insulation is above
regular value in accordance with relevant local and national
regulations.
For those doing pipe work
1 Make sure piping size is correct.
See
"4.3 Refrigerant pipe size and allowable length" on page 11
and
"4.3.3 To select refrigerant branch kits" on page
2 Make sure insulation work is done.
See
"5.5 To insulate the refrigerant piping" on page
3 Make sure there is no faulty refrigerant piping.
See
"5.3 Refrigerant piping" on page
7

Configuration

1
2
3
4
5
7 .1

Overview: Configuration

6
7
8
This chapter describes what you have to do and know to configure
9
the system after it is installed.
10
It contains information about:
▪ Making field settings
▪ Using the leak detection function
INFORMATION
It is important that all information in this chapter is read
sequentially by the installer and that the system is
configured as applicable.
DANGER: RISK OF ELECTROCUTION
7 .2

Making field settings

7 .2 .1

About making field settings

INFORMATION
The LEDs and buttons are located in the refrigerant
module.
7 .2 .2

Field setting components

Location of the 7-segment displays, buttons and DIP switches:
a
b
BS1 BS2
BS3
BS1
MODE: For changing the set mode
BS2
SET: For field setting
BS3
RETURN: For field setting
DS1, DS2
DIP switches
a
7-segment displays
b
Push buttons
7 .2 .3

To access the field setting components

It is not required to open the complete electronic component box to
access the push buttons on the PCB and read out the 7-segment
display(s).
19.
DS1 DS2
X27A
RWEQ96~432TATJU + RWEQ96~432TAYDU
VRV W T-Series water-cooled system air conditioner
4P484115-1A – 2017.10