Starting Automatic Mode; Operation; Operating Modes; Automatic Mode - Reflex Servitec 35-95 Manual De Instrucciones Original

Vacío - desgasificación pulverizadora
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 327
Only displayed if "Softening" or "Desalination" has
been selected in the "Water treatment" menu
option.
The attainable soft water capacity is calculated
from the type of softening used and the specified
hardness reduction.
Fillsoft I : Soft water capacity ≤
6000/hardness red. l
Fillsoft II : Soft water capacity ≤
12000/hardness red. l
Fillsoft Zero I : Soft water capacity ≤
3000/hardness red. l
Fillsoft Zero II : Soft water capacity ≤
6000/hardness red. l
Enter the value in the controller. Consult the
manufacturer information for third-party
products.
Only displayed if "Softening" or "Desalination" has
been selected in the "Soft water capacity" menu
option.
Available soft water capacity.
Only displayed if "Softening" or "Desalination" has
been selected in the "Soft water capacity" menu
option.
Manufacturer specification for the replacement
interval of the softening cartridges, regardless of
the calculated soft water capacity. The system
displays the "Softening" message.
Recommended maintenance message.
Off:
Without maintenance recommendation.
001 –
Maintenance recommendation in
060:
months.
For the output of messages to the floating contact,
see chapter 8.2.4 "Messages" on page 37 .
yes:
Output of all messages.
Output of all messages identified
no:
with "xxx" ("01", for example).
Switch to the Change Rem. Data menu option or
switch to the next menu option.
Switch to the fault memory or into the next main
menu option.
The last 20 alarms are stored with fault type, date,
time, and fault code.
See the chapter "Messages" for more information
about the ER... messages.
Switch to the parameter memory or into the next
main menu option.
The last 10 entries of the minimum working
pressure are stored with date and time.
Position of the "CD" motorized ball valve at the
pressure side of the pump to
the controller of the degassing process.
Information about the software version.
7.9
Cap. soft water
Automatic mode can be started as soon as the system is filled with water and the
gases contained have been vented.
During commissioning, continuous degassing is automatically activated to
remove any residual free or dissolved gases from the system. This time can be set
in the Customer menu as required by the system conditions. The default setting
is 24 hours. Subsequent to the continuous degassing, the device automatically
switches to interval degassing.


Remaining cap. soft
8
w.
8.1
8.1.1
Replacement in
Upon successful commissioning, you can activate the automatic mode with the
degassing functions and, optionally, the automatic make-up. The Servitec
controller monitors the functions. Faults are displayed and evaluated.
For automatic mode, you can set three different degassing programmes in the
Customer menu, see chapter 8.2.1 "Customer menu" on page 36 . Relevant
information is displayed in the message line of the controller display.
Next maintenance
Continuous degassing of the system water
Select this programme after commissioning and
repairs of the connected system. The device will
continuously degas for a set period of time. Free
and dissolved gases are quickly removed. Upon
request of make-up, make-up degassing is
Floating fault contact
automatically activated for the set make-up
time. In "Magcontrol" mode, the pressure is
monitored and displayed.
Start/setting:
Change Rem. data
(015)
Fault memory
ER 01...xx
Interval degassing of the system water
Designed for continuous operation. An interval
comprises a number of degassing cycles, with
the number to be set in the Service menu. An
Parameter memory
idling time follows an interval. The daily start of
the interval degassing can be set to a specific
time.
P0 = xx.x bar
Start/setting:
Pos. motorized ball
valve
Servitec 35-95
Vacuum spray degassing — 24.04.2020 - Rev. A
St arting Automatic mode
Press "Auto" on the controller's operator panel.
Note!
The commissioning process is now concluded.
Notice!
The "ST" dirt trap in the "DC" degassing line must be cleaned after the
expiry of the continuous degassing time at the latest, see chapter 9.2
"Schmutzfänger reinigen" on page 20 .
Ope ration

Operating modes

A utomatic mode
Automatic start after execution of the
start routine during commissioning.
Activated from the Customer menu.
Degassing time. Can be set in the
Customer menu, dependent on the actual
system. The default setting is 24 hours.
After expiry of the set time, the device
automatically switches to interval
degassing.
Automatic activation upon expiry of
continuous degassing.
Degassing cycles: 8 cycles per interval, to
be set in the Service menu.
Start time interval: To be set in the Servi c e
menu.
Idling time between intervals: To be set in
the Service menu.

Operation

Continuous degassing
Interval degassing
English — 35

Publicidad

Tabla de contenido
loading

Productos relacionados para Reflex Servitec 35-95

Tabla de contenido