Operation
E R
A larm
Code
11
Back-up volume
12
Filling time
13
Filling volume
14
Discharge period
15
Make-up valve
16
Power failure
19
Stop ˃ 4 hours
Maximum make-up
20
quantity
Maintenance
21
recommended
24
Water treatment
26

Conductivity measurement

27
Conductivity exceeded
30
I/O module fault
31
EEPROM defective
32
Undervoltage
33
Adjustment parameter
Main board communication
34
faulty
35
Digital input voltage faulty
Analogue input voltage
36
faulty
37
Input voltage MKH1
38 — English
F loating
Ca use
contact
"With water meter" must be activated in the
-
Customer menu.
Set value exceeded.
Severe water loss in the system.
Set value for the maximum filling duration has
-
been exceeded
-
Set value exceeded.
-
Set value exceeded.
"DC" degassing line closed.
Dirt trap clogged.
Contact water meter measures without make-
-
up request.
-
No power.
-
Device is in stop mode for more than 4 hours.
-
Set value exceeded.
-
Set value exceeded.
Set value for soft water capacity
-
exceeded.
Time interval for replacement of the
cartridge exceeded.
-
Measured value outside the measuring range.
-
Set value exceeded.
Cartridge capacity expired.
-
I/O module defective.
Connection between option card and
controller faulty.
Option card defective.
Yes
EEPROM defective.
Internal calculation error.
Yes
Supply voltage not achieved.
-
EPROM parameter memory defective.
-
Connecting cable defective.
Main board defective.
-
Short-circuit of input voltage.
-
Short-circuit of input voltage.
-
Short-circuit of input voltage.
Vacuum spray degassing — 24.04.2020 - Rev. A
Re medy
Check set value in the Customer or Service
menu.
Check the water loss and correct, if necessary.
Check set value in the Customer or Service
menu.
Check the water loss and correct, if necessary.
Check set value in the Customer or Service
menu.
Check the water loss and correct, if necessary.
Check set value in the Customer or Service
menu.
Open the degassing pipe.
Clean the dirt trap.
Check the 2-way motorized ball valve (WV) for
leaks.
Connect to power supply.
Set the controller to Automatic mode.
Reset the "Make-up quantity" meter in the
Customer menu.
Carry out maintenance.
Replace the softening cartridges.
Check set value in the Customer or Service
menu.
Check the sensor and cabling.
Check set value in the Customer or Service
menu.
Replace cartridge.
Replace the I/O module.
Check the connection between option card
and controller.
Replace the option card.
Inform Reflex Customer Service.
Check power supply.
Inform Reflex Customer Service.
Inform Reflex Customer Service.
Check the wiring at the digital inputs (water meter,
for example).
Check the wiring at the analogue inputs
(pressure/conductivity).
Check the wiring of the 2-way motorized ball valve.
A larm
re set
Quit
Quit
Quit
Quit
Quit
-
-
Quit
Quit
-
-
-
-
-
-
Quit
Quit
-
-
-