Pa rameter
S e tting
Maximum make-up
0 Litres
quantity
Soft water capacity
0 Litres
Cartridge replacement
18 months
Desalination (only if "Water treatment" with "Desalination")
Conductivity monitoring
No
Shut off make-up
No
Hardness reduction
8°dH
Maximum make-up
0 Litres
quantity
Soft water capacity
0 Litres
Cartridge replacement
18 months
Next maintenance
12 months
Volt-free contact
Yes
8.2.4
M e ssages
The display provides alarms in plain text and the ER codes listed below. Use the arrow buttons to scroll through multiple alarms displayed at the same time.
The fault memory stores the last 20 alarms for review, see chapter 8.2.1 "Customer menu" on page 36.
Alarm causes can be eliminated by the operator or a specialist workshop. Please contact the Reflex customer service for alarms that cannot be repaired.
Note!
Some messages must be acknowledged with the "Quit" key on the operator panel of the controller (see following table), after the cause has been
corrected. All other alarms are automatically reset as soon as the cause has been eliminated.
Note!
Floating contacts, setting in the Customer menu,see chapter 8.2.1 "Customer menu" on page 36.
E R
A larm
Code
01
Minimum pressure
02.1
Insufficient water
02.2
Insufficient water
02.4
Insufficient water
04.1
Pump
06
Make-up time
07
Make-up cycles
08
Pressure measurement
10
Maximum pressure
Re marks
Attainable make-up quantity
Attainable water capacity
Replace cartridge
In the case of soft water
residual capacity = 0
= Target – Actual
Attainable make-up quantity
Attainable water capacity
Replace cartridge
Time left to the next due
maintenance
Only the messages marked in
the "Messages" list
F loating
Ca use
contact
Yes
For "Magcontrol" setting only.
•
Set value not reached.
•
Water loss in the system.
•
Pump fault.
•
Expansion vessel defective.
Dry running protection: Insufficient water
-
switch
•
Defective.
•
Not cabled.
•
Triggered for too long.
Dry running protection: Insufficient water
-
switch has actuated too often.
-
Vacuum during make-up feed.
Yes
Pump disabled.
•
Pump jammed.
•
Pump motor defective.
•
Fuse defective.
-
•
Set value exceeded.
•
Water loss in the system.
•
Make-up line not connected.
•
Make-up rate insufficient.
-
Continuous water loss in the system.
-
•
Controller receives incorrect signal.
-
For "Magcontrol" setting only.
•
Set value exceeded.
Vacuum spray degassing — 24.04.2020 - Rev. A
S e rvice menu
Pa rameter
S e tting
Make-up
Pressure differential,
0.2 bar
"NSP" make-up
Pressure differential,
0.3 bar
filling pressure PF – P0
Maximum filling duration 10 h
Degassing
Idling times between
12 hours
degassing intervals
Number of degassing
n = 8
cycles for each interval
Daily start
08:00 h
Next maintenance
12 months
Volt-free contact
YES
•
Check set value in the Customer or Service
menu.
•
Check water level.
•
Check pump.
•
Check expansion vessel.
•
Check insufficient water switch.
•
Open the degassing pipe.
•
Clean the dirt trap.
•
Replace the degassing valve.
•
Clean the dirt trap.
•
Replace the degassing valve.
Open the make-up ball valve.
•
Rotate the pump with screwdriver.
•
Electrically test the pump motor.
•
Replace the 10 A fuse.
•
Check set value in the Customer or Service
menu.
•
Check water level.
•
Connect make-up line.
•
Check set value in the Customer or Service
menu.
•
Seal the leak in the system.
•
Check/connect the plug connection at the
pressure transmitter
•
Check the cable for damage.
•
Check the pressure sensor.
•
Check set value in the Customer or Service
menu.
•
Set the actuating pressure of the safety valve.
Operation
Re marks
Only Magcontrol
Only Magcontrol
Only Magcontrol
Idling times between the
degassing intervals
Number of degassing cycles in
one interval
Start of the daily degassing
intervals
Time left to the next due
maintenance
Only the messages marked in the
message list
A larm
Re medy
re set
-
Quit
Quit
-
Quit
Quit
Quit
Quit
-
English — 37