Gas Supply Line - baltur TBML80 PN Manual De Instrucciones

Quemador mixto gas igasoleo
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

GAS SUPPLY LINE

E
The gas supply scheme is shown in the diagram below.
N
The gas train is certified in accordance with regulation
EN 676 and is supplied separately from the burner.
G
A manual shut off valve, an interception valve and an anti-
L
vibration joint must be installed upstream of the gas valve, as
shown in the diagram.
I
S
GENERAL GAS BURNER SYSTEM
H
Legend
1) Manual shut off valve
2) Anti-vibration joint
3) Gas filter
4) Minimum gas pressure switch
5) Safety valve
6) Pressure regulator
Gas train supplied by the manufacturer
7) Valve seal control device (obligatory for burner with maximum
nominal thermal out-put over 1200 kW)
8) Pneumatic working valve
9) Control servomotor
10) Air adjustment gate
11) Air pressure switch
12) Combustion head
8 / 28
0006081470_201105
Responsibility of the installer