Wiring Diagram - baltur TBML80 PN Manual De Instrucciones

Quemador mixto gas igasoleo
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

CAM REGULATION ON SERVOMOTOR SQN 30.401
E
N
G
L
I
S
H
1 On/Off lever for motor-camshaft coupling.
2 Reference Index
3 - Position Indicator
I
Cam for maximum air aperture adjustment (70°)
II Total air closure (burner off) (0°)
III Cam for minimum air aperture adjustment (20°)
IV 1
flame diesel oil adjustment cam (30°)
st
V Cam to energize 2
nd
To modify the regulation of the 3 cams used, turn the respective red rings
(I - II - III....). The scale on the red ring indicates on the respective reference
scale the rotation angle set for each cam.
CAM REGULATION ON SERVOMOTOR STA5B0.36/83N23

1 Wiring Diagram

2 Adjusting screw
3 Unused Cam
4 Unused Cam
5 Gas ignition cam factory preset to 35°, can be modified to
improve the conditions of ignition +/- 5°
6 Gas operation cam preset to 90° (should not be changed)
7 Electrical connections
8 Reference Index
To modify the adjustment of the cams operate the respective screws.
The scale on the red ring indicates on the respective reference
scale the rotation angle set for each cam.
flame diesel oil valve (greater than cam IV) (50°)
22 / 28
0006081470_201105
ADJUSTABLE CAMS