baltur TBML80 PN Manual De Instrucciones página 18

Quemador mixto gas igasoleo
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

CONTROL EQUIPMENT AND COMMANDS FOR GAS BURNERS LME 22...
E
Status indication
N
Status
G
Waiting time "tw", other waiting states
Ignition phase, controlled ignition
L
Operation, flame O.K.
Operation, flame not O.K.
Extraneous light upon burner startup
I
Low voltage
Breakdown, alarm
S
Error code generation (see "Error code table")
Interface diagnostics
H
Legend
.... Fixed activation
¡ Off
Operation, instructions, diagnostics (con-
tinued from previous page)
Diagnostics of the cause of fault
After lockout, the red fault signal light will remain fixed on.
In this condition visual diagnostics of the cause of fault ac-
cording to the error code table can be activated by holding
down the lockout reset button for more than 3 seconds.
Holding down the reset button again for at least 3 seconds,
interface diagnostics will be activated
Color code table for multicolor signal
lamp (LED)
2 blinks
l l
3 x blinks
l l l
4 blinks
l l l l
5 blinks
l l l l l
6 blinks
l l l l l l
7 blinks
l l l l l l l
8 x blinks
l l l l l l l l
9 blinks
l l l l l l l l l
10 blinks
l l l l l l l l l l
During the time the cause of fault is diagnosed, the control outputs are deactivated
- Burner remains shut down
- External fault indication remains deactivated
- Fault status signal "AL" at terminal 10, according to the error code table
To exit from the diagnostics of the cause of fault and switch on the burner again, reset the burner control.
Hold down the lockout reset button for about 1 second (< 3 seconds).
Equipment and
Safety time
programmer
LME 22.233C2
During startup, status indication takes place according to the following table:
Color code table for multicolor signal lamp (LED)
Red
Yellow
l
Green
n
«AL» at term. 10
On
On
On
On
On
On
On
On
Off
Preventilation
Pre-
time
ignition
3
30
2
Color code
¡...............................................
l
¡
l
¡
l
¡
l
¡
l
¡
¡...............................................
n
¡
n
¡
n
¡
n
¡
n
¡
n
n
n
n
n
l
l
l
l
l
.........................................
¡
¡
¡
¡
Blocked position
Blocked position
Code error table
Error code table
Possible cause
No flame at the end of the "TSA" (safe ignition time)
- Faulty or soiled fuel valves - Faulty or soiled flame detector
- Poor adjustment of burner, no fuel
- Faulty ignition equipment
defective "LP" (air pressure switch)
- No or faulty air pressure signal after completion "t10"
- "LP" is welded in normal position
Extraneous light upon burner startup
Time out "LP" - "LP" is welded into working position
Unused
Too many losses of flame during operation (limitation of repetitions)
- Faulty or soiled fuel valves - Faulty or soiled flame detector
- Poor adjustment of burner
Unused
Unused
Wiring error or internal error, output contacts, other faults
Time between open-
Post-
ing of 1
flame valve
st
ignition
and 2
flame valve
nd
2
11
14 / 28
0006081470_201105
Color
Off
Blinking yellow led
Green
Blinking green led
Green-red
Yellow-red led
Red
Blinking red light
Flashing red light
Blocked position
Visual diagnostic
PC/analyzer
Diagnostic
interface
Air shutter open-
Air shutter closing
ing stroke time
30
stroke time
30

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Tbml160 pn

Tabla de contenido