Checking Operation Of The Diesel Motor Pump; Sets With Several Pumps; Periodic Maintenance - DAB 1 KDN Instrucciones Para La Instalación Y El Mantenimiento

Grupos de bombas contra incendios
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 86
To check the direction of rotation of the compensating electropump (or pilot pump), turn its selector to MAN for a few moments
and check that, when viewed from the fan side, the motor is turning in a clockwise direction.
If not, exchange on the terminal board any two leads of the power supply of the panel for the compensating electropump (or
pilot pump).
b) Turn the selector on the electropump panel to AUT position.
c) Turn on a hydrant in the system.
d) Check that the compensating electropump (or pilot pump) starts.
e) Turn off the hydrant.
f)
Check that the electropump stops AUTOMATICALLY.

5.3 CHECKING OPERATION OF THE DIESEL MOTOR PUMP

a) Turn the main switch on the Diesel motor pump panel to 1 (ON).
A 230V electric heater (located under the oil sump for air-cooled motors or in the head for water-cooled motors) will bring the oil (or water)
to a minimum temperature, so as to facilitate starting of the motor pump.
When the Diesel motor pump is started up on the site for the first time, it is necessary to check the failed start alarm. (EN
12845 10.9.13.2 – UNI 10779) See the Electric Panel instructions booklet for further information.
b) Turn the selector on the Diesel motor pump panel to AUT position.
c) Open a valve in the system (or the pump manual start valve – ref. 5)
d) Check that the motor pump starts.
e) Close the valve in the system (or the pump manual start valve – ref. 5).
f)
Check that the number of rpm, shown on the display, corresponds to the value indicated on the data plate on the accelerator control,
if necessary regulate the accelerator according to the indication on the plate.
g) Put the system under pressure.
h) Stop the motor pump with the STOP button on the electric panel.
ATTENTION: DURING OPERATION OF THE DIESEL MOTOR PUMP:
Check for any water leaks in the system and stop the motor pump if necessary.
The contact that indicates when the motor pump is running closes and may activate any connected alarms.
If it fails to start, the Diesel motor pump makes six attempts to start alternately on the two batteries (EN 12845 point 10.9.7.2 – UNI 10779).
The condition of Diesel motor pump running is detected by the speed sensor on the motor.
If the motor pump does not start after six attempts, the electric panel activates:
a failed start warning light,
a failed start alarm contact.

5.4 SETS WITH SEVERAL PUMPS

Standard EN 12845 – UNI 10779 contemplates various solutions with one or more pumps having similar characteristics:
if TWO pumps are installed, each pump supplies the total flow rate of the system (100%),
if THREE pumps are installed, each pump supplies 50% of the total flow rate.
Also, in sets where more than one pump is installed with superior or duplicate water supply, only one pump will be electric (10.2).
From this it may be deduced that, in the case of a superior or duplicated supply, the sets will be composed of:
a)
1 electropump (100%),
b)
1 Diesel motor pump (100%),
c)
1 electropump + 1 Diesel motor pump (each supplies 100%),
d)
1 electropump + 2 Diesel motor pumps (each supplies 50%),
e)
3 Diesel motor pumps (each supplies 50%),
In the case of a single supply, there are no limits to the number of electropumps.
DAB supplies the sets in a "modular" version, in separate units, so as to be able to make up all the versions mentioned above. By means of
the JOINING MANIFOLD (see drawing on page 32) it is possible to join the manifolds so as to obtain a single delivery manifold.
The intakes, the electric panels, etc. remain separate as contemplated by standard EN 12845 – UNI 10779.

6. PERIODIC MAINTENANCE

The whole fire-fighting system to standard EN 12845 – UNI 10779, including the set of fire-fighting pumps, must always be kept in perfect
working order. For this reason, regular maintenance is of particular importance.
According to standard EN 12845 point 20.1.1 – UNI 10779, the user must:
-
carry out a programme of inspections and checks;
-
arrange a testing, assistance and maintenance programme,
-
document and record the activities, filing the documents in a special register kept in the building.
The user must ensure that the testing, assistance and maintenance programme is carried out under contract by the installer of the system or by
a company with the same qualifications.
6.1 WEEKLY CHECK (to be carried out at intervals of no more than 7 days)
The weekly check of the fire-fighting set to standard EN 12845 – UNI 10779 contemplates checking and noting down the following values:
-
pressure of pressure gauges,
-
water level in the tanks – water reserves,
-
correct position of the interception valves.
-
To test the automatic starting of the pumps, proceed as described below:
-
Check the levels of the fuel and lubricating oil in the Diesel motors.
-
Open the pump manual start valve (ref. 5).
-
Check that the pump starts and make a note of the starting pressure.
ENGLISH
45

Publicidad

Tabla de contenido
loading

Tabla de contenido