8.6
Adjustment - Manual operation
Installation and operating instructions Wilo-Stratos MAXO/-D/-Z
Setting the control functions
Settings menu
Setback operation
Visible for active control modes, which
support additional control function "auto-
matic setback operation". (See table "Pre-
defined applications in the settings as-
sistant").
No-Flow Stop
Visible for active control modes, which
support the additional function "No-Flow
Stop". (See table "Pre-defined applica-
tions in the settings assistant").
Q-Limit
Max
Visible for active control modes, which
support additional control function "Q-
Limit
". (See table "Pre-defined applica-
Max
tions in the settings assistant").
Q-Limit
Min
Visible for active control modes, which
support the additional control function
"Q-Limit
". (See table "Pre-defined ap-
Min
plications in the settings assistant").
Detection of disinfection
Visible for active control modes, which
support the additional control function
"Detection of disinfection". (See table
"Pre-defined applications in the settings
assistant").
Emergency operation speed
Visible for active control modes that reset
to a fixed speed.
PID parameter Kp
Visible for user-defined PID control.
PID parameter: Ki
Visible for user-defined PID control.
PID parameter Kd
Visible for user-defined PID control.
PID: Inversion
Visible for user-defined PID control.
Pump ON/OFF
Always visible.
Table 24: Settings menu - Set auto control
All control modes, which are selected via the settings assistant, can be overridden with
the functions of manual operation OFF, MIN, MAX, MANUAL.
Functions of manual operation can be selected in menu
ation"
"Manual operation (OFF, MIN, MAX, MANUAL)":
Function
Description
Pump works according to the set controls.
Auto control mode
Pump is switched off. Pump is not running.
OFF
All other set controls will be overridden.
Pump is set to minimum power.
MIN
All other set controls will be overridden.
Description
Setting automatic detection of setback
operation.
Setting automatic detection of closed
valves (no flow).
Setting an upper threshold of the volume
flow.
Setting a lower threshold of the volume
flow.
Setting automatic detection of thermal
disinfection to facilitate flushing.
The pump automatically switches to this
constant speed if the set control mode
fails (e.g. sensor signal fault).
Setting the Kp factor for the user-defined
PID control.
Setting the Ki factor for the user-defined
PID control.
Setting the Kd factor for the user-defined
PID control.
Setting the inversion for the user-defined
PID control.
Switching the pump on/off with low pri-
ority. A MAX, MIN, MANUAL override
switches the pump on.
"Settings"→ "Manual oper-
en
175