Technical Data - Wilo Stratos MAXO Serie Instrucciones De Instalación Y Funcionamiento

Ocultar thumbs Ver también para Stratos MAXO Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 442
en
2.3

Technical data

120
Description of the pump
Example: Stratos MAXO-D 32/0,5-12
Single pump
-D
Double pump
-Z
Single pump for domestic hot water circulation systems
Flange connection DN 32
32
Screwed connection: 25 (RP 1), 30 (RP 1¼)
Flange connection: DN 32, 40, 50, 65, 80, 100
Combination flange: DN 32, 40, 50, 65
0,5: minimum delivery head in m
0,5-12
12: maximum delivery head in m
at Q = 0 m³/h
Table 2: Type key
Technical data for heating/air conditioning/cooling
Fig. 4: Technical data for heating/air conditioning/cooling
Technical data
Permissible fluid temperature
Permitted ambient temperature
Maximum relative humidity
Mains voltage
Residual current ∆I
Electromagnetic compatibility
Emissions-sound-pressure level
Energy efficiency index (EEI)
Temperature class
Pollution degree
Max. permitted operating pressure
*
EEI value of the pump is achieved when the display is switched off.
1)
Standard version
2)
Special version or auxiliary equipment (at additional charge)
Table 3: Technical data for heating/air conditioning/cooling
-10 to +110 °C
-10 to +40 °C
95 % (non-condensing)
1~ 230 V +/-10 % 50/60 Hz
≤ 3.5 mA
Emitted interference in acc. with:
EN 61800-3:2004+A1:2012 / residential
environment (C1)
Interference resistance in acc. with:
EN 61800-3:2004+A1:2012 / industrial en-
vironment (C2)
< 54 dB(A)
*
≤ 0.17 to ≤ 0.19 (depends on type)
TF110 (see IEC60335-2-51)
2 (IEC 60664-1)
1)
PN 6/10
, PN 16
2)
WILO SE 2018-11

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Stratos maxo-d 32/0,5-12Stratos maxo-z 32/0,5-12

Tabla de contenido