Configuration warnings
216
Faults, causes, remedies
Code
Fault
Too many wrong PIN
entries.
580
Additional information about causes and remedy:
An incorrect PIN has been entered more than 5 times.
For safety reasons, further connection attempts are prevented without a re-
start.
Double pump does not
fit.
581
Additional information about causes and remedy:
Double pump function is only possible with two pumps of the same type.
Double pump is not
compatible.
582
Additional information about causes and remedy:
Double pump function is only possible with two compatible pumps of the
same type.
Fluid temperature too
high.
583
Additional information about causes and remedy:
High fluid temperatures lead to significant damage to the pump.
1)
MFA
partner type is not
appropriate.
Additional information about causes and remedy:
590
A maximum replacement flow is provided for the Multi-Flow Adaptation
partner.
Check the partners highlighted with (!) in the MFA
menu.
Table 48: Warning messages
1)
MFA= Multi-Flow Adaptation
Configuration warnings occur if an incomplete or contradictory configuration has been
made.
Example:
The "Hall temperature control" function requires a temperature sensor. The corre-
sponding source is not specified or not correctly configured.
Code
Fault
Setpoint source not
suitably configured.
601
The setpoint source is not correctly configured. In the context menu there is
a link for configuring the setpoint source.
Setpoint source not
available.
602
The setpoint source or the CIF module is not correctly configured. In the con-
text menu there are links for configuration.
Sensor source not suit-
ably configured.
603
The sensor source is not correctly configured. In the context menu there is a
link for configuring the sensor source.
Cause
Remedy
Too many connection
Disconnect power supply
attempts with wrong
from the pump and switch
PIN.
it on again.
The double pump
Select/install appropriate
partner does not fit
double pump partner.
this type of pump.
Double pump partner
Select/install appropriate
is not compatible
double pump partner.
with this pump.
Fluid temperature is
Reduce fluid temperature.
hotter than 110 °C.
1)
A MFA
partner does
Check type and software
not the appropriate
of the partner pump.
type.
1)
overview of the context
Cause
Remedy
Setpoint is not con-
Configure source or
nected to correct
select another source.
source. Input is not
correctly configured.
Setpoint not connec-
Insert CIF module.
ted to existing CIF
Activate CIF module.
module.
Sensor 1 is not con-
Configure source.
nected to correct
Select other source.
source. Input is not
correctly configured.