Operating instructions
IN4000 Direct
Fig. 6: Maximum
cable length
Tab. 7: Maximum
cable length
8012183/ZWH0/2018-06-05
Subject to change without notice
Electrical installation and
adjustment
5.3.2
Maximum cable length
Taking into account the specified cable resistance, the
following cable lengths are allowed as a function of the
output current I
out
PLC
I
[mA]
out
Possible output
current per
channel
OUT1/OUT2
20
30
40
50
70
90
100
© SICK AG • Germany • All rights reserved
per channel (see Tab. 7).
L
[m]
1
Maximum cable
length (see
section 5.3.1,
page 74)
65
45
30
25
18
15
12
en
Chapter 5
R
[Ω]
max
Maximum
permissible cable
resistance
6.4
4.4
3.2
2.6
1.8
1.4
1.3
75