Troubleshooting: DALI Functions
Symptom
Possible Causes
"Build System" command
D1 and/or D2 are miswired or not connected
does not find DALI loads
Cannot add a DALI device
Zone is not set to Digital
to a zone after a "Build
System" or "Address all"
command has been run
DALI device at full
D1 and D2 are not connected
brightness cannot be
DALI link is overloaded
controlled
DALI devices do not flash
DALI devices are not addressed
when running the "Build
DALI devices are miswired
System" command
DALI device is not
DALI device is not addressed
affected by a zone level
DALI device is not assigned to a zone
change
DALI device light levels
DALI device is being affected by the daylight
can be lowered, but not
sensors
raised to full On
®
Solution
Check wiring; if wiring is correct, call Lutron Technical Support
Set the zone to Digital
Check D1 and D2 connections on the back of the GRAFIK Eye
Reduce number of DALI devices on link to 64 or fewer.
Check voltage: Minimum voltage of 12 V
Address DALI devices
Check D1 and D2 wiring, and power wiring to DALI devices
Run the "Address all" command and assign the DALI device to a zone
Assign DALI device to a zone
Recalibrate the associated daylight sensors
For additional information, see the complete installation and operation guide at www.lutron.com/qs
GRAFIK Eye
QS with DALI Control Unit Quick Installation and Operation Guide 23
®