Wiring the GRAFIK Eye
QS Link Control Wiring Details
• System communication uses IEC PELV wiring.
• Follow all local and national electrical codes when
installing IEC PELV wiring with line voltage/mains
wiring.
• Each terminal accepts up to two 1.0 mm
• Total length of control link must not exceed 610 m.
• Make all connections in the control unit's wallbox.
• Wiring can be T-tapped or daisy-chained.
• IEC PELV 24 V
150 mA.
System Limits
The QS wired communication link is limited to 100
devices or 100 zones.
The GRAFIK Eye
QS control unit supplies 3 Power
®
Draw Units (PDUs) on the QS link. Refer to the
QS Link Power Draw Units specification submittal
(Lutron PN 369405) for more information concerning
Power Draw Units.
Wire Sizes (check compatibility in your area)
QS Link Wiring Length
Less than 153 m
153 to 610 m
®
QS with DALI Control Unit:
®
wires.
2
Wire Gauge
Power (terminals 1 and 2)
1 pair 1.0 mm
2
Data (terminals 3 and 4)
1 twisted, shielded pair 0.5 mm
Power (terminals 1 and 2)
1 pair 4.0 mm
2
Data (terminals 3 and 4)
1 twisted, shielded pair 0.5 mm
For additional information, see the complete installation and operation guide at www.lutron.com/qs
GRAFIK Eye
LUTRON
LUTRON
GRAFIK Eye
with DALI
control unit
QS smart
power
panel
Sivoia
QS
®
window
treatment/
drape
Daisy-Chain Wiring Example
To DALI link 1
GRAFIK Eye
QS
®
with DALI
control unit
LUTRON
Lutron Cable Part Number
GRX-CBL-346S
GRX-PCBL-346S
2
GRX-CBL-46L
GRX-PCBL-46L
2
QS with DALI Control Unit Quick Installation and Operation Guide 7
®
LUTRON
LUTRON
LUTRON
LUTRON
T-Tap Wiring Example
To DALI link 1
seeTouch
QS
®
wallstation
LUTRON
To DALI
LUTRON
link 2
LUTRON
LUTRON
LUTRON
To DALI link 2
GRAFIK Eye
QS
Sivoia
®
®
with DALI
QS window
control unit
treatment/
drape
LUTRON
LUTRON
LUTRON
QS smart
power panel
LUTRON
LUTRON
LUTRON
LUTRON
QS
®
seeTouch
QS
®
wallstations
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON