Code
No.
Name
c61
Present status/error
c62
Last error
c63
Last error but one
Last error but two
c64
Configuration TRIP
c70
reset (error reset)
Auto-TRIP reset
c71
delay
c73
Input voltage
selection
c78
Operating time
counter
c79
Mains connection
time counter
S-ramp integration
c82
time
Skip frequency 1
L25
Skip frequency 2
L26
L28
Skip frequency
bandwidth
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES
Possible Settings
Lenze Selection
status/error message
error message
0
0
TRIP reset after LOW-HIGH change at
terminal 28, mains switching, or after
LOW-HIGH change at digital input "TRIP
reset"
1
Auto-TRIP reset
WARNING!
Automatic starting/restarting may cause damage to equipment and/or injury to
personnel! Automatic starting/restarting should only be used on equipment that
is inaccessible to personnel.
0.0
0.0
{s}
0
Low (for 200 V input)
1
High (for 230 V input)
Display
Total time in status "Start"
Display
Total time of mains = on
0.0
0.0
{s}
0.0
0.0
{Hz}
0.0
0.0
{Hz}
0.0
0.0
{Hz}
Note
Bandwidth (Hz) = f
s
Example: L25 = 18 Hz and L28 = 4 Hz; the bandwidth = 18...22 Hz
Commissioning
• Display
• Refer to Section 5 for explanation
• Auto-TRIP reset after the time
• More than 8 errors in 10 minutes
See c70
60.0
• Lenze setting depends on C93
• During commissioning, confirm
0...999 h: format xxx
1000...9999 h: format x.xx (x1000)
10000...99999 h: format xx.x (x1000)
50.0
• c82 = 0.0: Linear accel/decel ramp
• c82 > 0.0: Adjusts S-ramp curve
240
• L25 and L26 define the start of the
• L28 defines the bandwidth of the
240
10.0
(Hz)
+
L28 (Hz)
f
= L25 or L26
s
IMPORTANT
of status and error messages
set in c71
will trigger
fault
rSt
correct setting based on mains
voltage
for smoother ramp
skip range
skip range