Sime Planet 25/60BF Instrucciones De Instalación página 98

Ocultar thumbs Ver también para Planet 25/60BF:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

SETTING THE D.H.W. PARAMETERS
Reduced D.H.W.
temperature value
D.H.W. filling
SERVICE VALUES
Final user level 2
programming block
Entrance function terminal 3-4
Operating mode of external contact
External and ambient
sensor influence
Anti-bacterial function
96
The hot water may be set to a reduced temperature value, such as
61
40°C, which is outside the comfort zone, such as 60°C (daily pro-
gramme 8).
0 = 24 hours/ day - Hot water is always available at the temperature set
62
with user parameter n°3.
1 = standard - Hot water according to the daily heating programme.
In the comfort areas of heating the temperature of the D.H.W. tank is
regulated to the value set with user parameter n° 3.
In the reduced areas of heating the temperature of the D.H.W. tank is
regulated to the value set with parameter n° 61 of the service level.
2 = service disconnected
3 = second daily programme (8) - Every day of the week the temperature of
the hot water is set according to programme 8. In this case there is a
single programming for all the days of the week and three time zones are
available. In the time spans set the temperature of the D.H.W. tank is
regulated according to that set in parameter n°3. In the remaining hours
the D.H.W. tank is controlled to the temperature set with parameter n°
61 the of service level.
This block (1) can be activated to display all the parameters without modif-
63
ying them. Pressing buttons
WARNING:
The activation block can be deactivated temporarily by pressing buttons
and
simultaneously; a confirmation sign appears on the display. At this
point press simultaneously the buttons
To permanently remove the activation block, set parameter 63 on 0.
The freely programmable input (terminals 3 and 4 of the socket) allows
64
three different functions to be activated. The parameter has the following
significance:
1 = If an external sensor is connected, the display will show the temperature
of the external sensor ( _ _ = no sensor connected, function disabled).
2 = With an external contact, it is possible to switch-over to "reduced pre-
set value of the ambient temperature".
3 = With an external contact, it is possible to switch-over to "reduced pre-
set value of the antifreeze ambient temperature" (short circuit 0 0 0 or
interruption _ _ _ ). The display shows the current status of the external
contact.
If the entrance (terminals 3 and 4 of the socket) is connected to a zero potential
65
external contact (parameter 64 = 2 or 3), the operating mode of the contact can
be determined (remote telephone switch or window contact). The operating
mode specifies the status of the contact in which the required function is active.
Display:
Operating mode closed (short circuit)
Operating mode open (interruption)
Determines the mix ratio between the internal and external ambient sensor
66
when parameter 64 = 1.
0 %
= internal sensor only active (0% external - 100% internal)
50 % = mean value of external + internal sensor
100 % = external sensor only active
The set mix is used for ambient control and display.
If the external sensor is short circuited or interrupted, the operation conti-
nues with the internal sensor.
This function allows the hot water to be brought to a high temperature once
69
a week in order to eliminate eventual pathogenic agents.
It is active every Monday for a maximum duration of 2.5 hours at a delivery
temperature of 65°C.
0 = not active
or
displays "OFF".
and
1 = active
for at least 5 seconds.
0 0 0
_ _ _

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Planet 30/60bf

Tabla de contenido