BTL5-A/C/E/G1_-M/U_ _ _ _-T-_S 32
Micropulse Linear Transducer - Rod Style
9
Resetting all values (Reset)
If an existing configuration needs to
be deleted, all values can be re-
stored to the original factory set-
tings (Reset).
Note:
The Reset procedure must be
performed individually for each
measuring unit.
Activate buttons:
1. Press one of the buttons for at
least 3 s. Release button.
2. Within 1 s hold down buttons 1+2
simultaneously for at least 3 s. Now
the Error value remains stored as
the output signal.
If an error occurs or there is an
interruption while activating a
button, please wait for an addi-
tional 12 s before starting over.
Perform reset:
3. Hold down both buttons for at least
6 s. The Null value is displayed, and
the reset has taken place.
4. Release buttons. The current posi-
tion value is displayed and the but-
tons are again deactivated.
The transducer is ready for new
calibration.
10
english
Displayed values (example)
at 0...10 V
5.39
5.39
>3 s
1
/ 2
<1 s
10.50
>3 s
1
+ 2
10.50
0.00
1
+ 2
>6 s
8.43
at 4...20 mA
Current
10.80
A
V
m
position value
Current
10.80
A
V
m
position value
Code =
3.60
A
V
m
Error value
Code =
3.60
A
V
m
Error value
4.00
Code =
V
A
m
Null value
Current
15.67
V
A
m
position value
(factory set-
ting)