• Check the working order of the level sensor
(float, minimum pressure switch, optional probe
module panel).
• Check for the presence (level) of water on the in-
take side.
• Check the water pressure on the intake side.
Text on
Model
the dis-
play (*)
A2
OVER
MMW
CURR
MTW
MMA
MTA
Troubleshooting: The converter supplies current to
the electric motor above the set rated value. The
converter protects the motor against current over-
load.
Solutions:
• Check the condition of the windings of the elec-
tric motor.
• Check the power consumption of the electric mo-
tor.
• Check the cross-section of the motor's power ca-
ble: this must be suited to the length of the cable
and to the power of the motor.
• Check configuration of the rated current parame-
ter.
• The value of the converter's rated current must
be at least equal to the current value on the data
plate. If the power cable for the motor is longer
than 30 meters, it is advisable to increase the
value by a minimum of 10%.
• para. A models MMW and MTW. See
MENU (MB)
parameters.
• para. NOM.CURR for models MMA and MTA.
See
BASIC MENU (MB)
WARNING:
If the value is not configured correctly,
the motor might NOT be protected
against overload and could suffer irrepar-
able damage.
Text on
Model
the dis-
play (*)
A3
MOTOR
MMW
DIS
MTW
Descrip-
Reset
tion
Overcur-
Automat-
rent on
ic. A max
the mo-
of 4 at-
tor side
tempts to
of the
start are
electric
made at
pump.
2 second
intervals.
Perma-
nent
locking
of the
electric
pump if
the alarm
contin-
ues to be
active af-
ter these
attempts.
BASIC
parameters.
Descrip-
Reset
tion
Electric

Manual.

motor
Text on
Model
the dis-
play (*)
MMA
MTA
An automatic function of the converter that detects
current consumption while the motor is running. The
converter cuts out the power supply to the motor and
remains locked.
Troubleshooting:
• In the case of single-phase motors, the thermal
circuit breaker (motor protector) trips automati-
cally. The circuit breaker is located in the terminal
box, a separate electrical panel or in the motor,
depending on the model of the electric pump (re-
fer to the relative manual).
• Breaking or failure of a phase of the motor.
• Failure/disconnection/deterioration of a phase of
the motor's power cable.
• Breaking of the converter's fuse, refer to
13
and
Figure 15
.
• For single-phase submerged motors with float.
Check the float to see if it is broken or has trip-
ped.
Text on
Model
the dis-
play (*)
A4
PRESS
MMW
MIN
MTW
MMA
MTA
The pressure of the system does not exceed the set
value of the MP (MMW/MTW) or (MMA, MTA) pa-
rameter. After the delay dL (MMW, MTW) or MP DE-
LAY (MMA, MTA), the pump is stopped and protect-
ed against dry running. The ART function is activat-
ed. See
Special
functions.
Troubleshooting:
• No water on the intake side of the pump: check
the level or pressure of the water.
• Pump not primed. Prime the pump.
• The pipe on the delivery side of the pump is bro-
ken. The flow of water is too high.
• The pump (impeller or diffuser) is damaged. Con-
tact the technical assistance service.
• The motor is damaged and must be replaced.
Text on
Model
the dis-
play (*)
A5
FAULT
MMW
SENS
MTW
MMA
MTA
Troubleshooting: The pressure sensor is faulty.
en - Original instructions
Descrip-
Reset
tion
discon-
nected
Figure
Descrip-
Reset
tion
Minimum
Automat-
pressure
ic, with
alarm
reset
tests.
Descrip-
Reset
tion
Fault
Automat-
with the
ic
pressure
sensor
39