PDM Installation

The following steps explain how to install the optional FC 6750 PDM.
1.
2.
NOTE The output of the PDM is 120/240V while the UPS and utility inputs are 200–240V.
3.
4.
5.
Input Connector
Bypass Switch
Voltage Selector Switch
PDM
UPS-Output
Connector
UPS
Figure 25. UPS and PDM Installation (FC 6750 PDM Model Shown)
®
EATON Powerware
Verify that the Bypass switch on the PDM is in the NORMAL
position (see Figure 25).
Select the input voltage (208 or 240V) using the Voltage Selector
Switch according to the utility voltage:
S
Utility voltage 200–208V, select 208V
S
Utility voltage 220–240V, select 240V
Verify that the power cord provided with the IBM equipment is
detached from the UPS input connector. Retain the cord for future
use.
Connect the jumper cable (provided in the PDM accessory kit) from
the 16A UPS output receptacle into the UPS-output connector on
the PDM.
Plug the attached PDM-to-UPS cord into the input connector on the
UPS rear panel.
Power Cord
PDM-to-UPS Cord
PDM Output Circuit Breaker
UPS Battery Connector
UPS Output Receptacle (16A, IEC 320-C19)
9125 (9910-P30) UPS Installation Guide for IBM
INSTALLATION
Output Receptacles
(Two L6-15R)
Output Receptacles
(Two 5-15R)
Output Receptacles
(Four 6-20R)
UPS Input Connector
(16A, IEC-320)
®
S
Applications