Setting The High Level; Stop Delay; Power-On Delay; Dry-Running Protection - Grundfos LC 241 Manual Del Usuario

Ocultar thumbs Ver también para LC 241:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

2.
Press OK once.
The current stop level is indicated on the display.
3.
Set the stop level using the Up and Down buttons.
4.
Continuously press OK to confirm all other settings and to exit
the setup.
If you are using the same level for the start and stop
level, remember to set a stop delay. This will prevent
the pump from starting and stopping too frequently.

6.5 Setting the high level

6.5.1 Setting the high level with Grundfos GO Remote
For analog sensors - :
1.
Go to Settings > Level control > High level
2.
Set the high level.
For digital sensors - a :
1.
Go to SettingsLC 231 IO terminals
2.
Select which terminal to configure.
6.5.2 Setting the high level with the operating panel
The settings apply to analog sensors
1.
Press and hold OK until the display starts flashing.
2.
Press OK four times. The current high level is indicated on the
display.
3.
Set the high level using the Up and Down button.
For digital sensors, enable or disable the setting.
1.
Press OK once to complete the setting.

6.6 Stop delay

The stop delay is the time from when the stop level is reached until
the pump stops. The stop delay prevents the pump from starting
and stopping too frequently and reduces water hammer in long
pipes.
6.6.1 Setting the stop delay with Grundfos GO Remote
1.
Select Settings > Level control > Stop delay > State
2.
Select Stop delay time.
3.
Set the Stop delay time.

6.7 Power-on delay

With this function it is possible to delay the startup of the pump after
the power supply has been switched on. The purpose is to avoid
disturbing the main power network which could happen if several
pumps start up immediately when the power supply is switched on.
6.7.1 Setting the power-on delay with Grundfos GO Remote
1.
Go to Settings > Power-on delay.
2.
Set the function to Enabled.
3.
Set the time delay.

6.8 Dry-running protection

If the pump is running and the liquid level in the tank or pit becomes
lower than the dry-running level, the dry-running protection will stop
the pump to ensure that it is not damaged.
Dry-running protection is dependent on a feedback signal from a
level sensor installed in the tank or pit.
6.8.1 Setting the dry-running level with Grundfos GO Remote
1.
Go to Settings > Level control > Dry-running level.
2.
Set the dry-running level.
18
The dry-running level must be set to a value which
ensures that the pump is not damaged due to dry-
running. The specific level depends on the installed
pump type. See the installation and operating
instructions for the product.
6.8.2 Setting the dry-running level with the operating panel
1.
Press and hold OK until the display starts flashing.
2.
Set the dry-running level using the Up or Down button.
3.
Continuously press OK to confirm all other settings and to exit
the setup.

6.9 Multipump settings

The control unit enables start and stop of the two pumps alternately.
The pump with the lowest number of running hours is always
started first. The function ensures that the running hours of the
pumps are the same.
It is possible to set a time delay before the next pump is started.
6.9.1 Setting the multipump settings with Grundfos GO Remote
1.
Go to Settings > Multi pump settings
2.
Set Inter pump delay.
This is the starting delay between the pumps ensuring that they
do not start at the same time.
3.
Set Max number of running pumps.
This is the maximum number of pumps which are allowed to
run at the same time.
6.10 Using the same level switch for the start and stop
level
1.
Set one digital input to Start pump 1 or Stop. All other digital
inputs must be disabled.
2.
Set a stop delay.
This will prevent the pump from starting and stopping too
frequently.

6.11 Antiseizing

The Anti-seizing function prevents a pump from choking or seizing
up as a result of deposits buildup. Anti-seizing is used in pits that
have had no inlet flow for a long period. The Anti-seizing function
ensures that the pump starts as often as set in Anti-seizing > >
Interval. The pump will operate for the number of seconds
indicated by the user.
6.11.1 Setting the "Anti-seizing" function with Grundfos GO
Remote
1.
Go to Settings > Anti-seizing.
2.
Set the function to Enabled.
3.
Set the time interval.
4.
Set the operating time.

6.12 Signal-detection time

The signal-detection time is the minimum time a level has to be
active before the control unit initiates an action, such as starting or
stopping a pump.
6.12.1 Setting the signal-detection time with Grundfos GO
Remote
1.
Go to Settings > Level control > Signal detection time.
2.
Set the signal-detection time.

Publicidad

Tabla de contenido
loading

Tabla de contenido