Dimension Drawings; Access The Air Intake Area - Kohler 14/20RESA Manual Del Usuario

Ocultar thumbs Ver también para 14/20RESA:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 126
Figure 1-2 gives the exhaust temperature at rated load.
The engine exhaust mixes with the generator set
cooling air at the exhaust end of the enclosure. Mount
the generator set so that the hot exhaust does not blow
on plants or other combustible materials. Maintain the
clearances shown in the dimension drawing in
Section 2.
Exhaust
Exhaust gas exiting the enclosure
at rated kW, _C (_F)
Figure 1-2 Exhaust Flow and Temperature
The generator set requires correct air flow for cooling
and combustion. The inlet and outlet openings in the
sound enclosure provide the cooling and combustion
air. Figure 1-3 shows the locations of the cooling air
intake and exhaust vents. Inspect the air inlet and outlet
openings inside and outside the enclosure to ensure
that the air flow is not blocked.
1
REAR VIEW
1. Air intake
2. Exhaust outlet
Figure 1-3 Cooling Air Intake and Exhaust
The generator set is designed to operate with all
enclosure panels and internal baffling in place. If during
installation, maintenance or repair the unit must be
operated without the complete enclosure and baffling as
shipped from the factory make sure the exhaust panel is
removed as well.

1.5 Dimension Drawings

See the dimension drawings in Section 2 for the
generator set dimensions, fuel and electric inlet
locations, and recommended clearance.
TP-6803 1/15
All manuals and user guides at all-guides.com
Temperature,
_C (_F)
260 (500)
1
2
tp6733

1.6 Access the Air Intake Area

The battery, fuel system, and electrical connections are
located in the air intake area. Raise the roof and remove
the enclosure panel to access the air intake area during
installation as described below.
1. Remove two screws from the top of the air intake
panel.
Pull the the panel up and off.
Figure 1-4.
2. To make the electrical connections, you will also
need to remove the cover panel over the terminal
block as shown in Section 1.9.3.
3. Reinstall the panels after all electrical connections
are complete and the battery is installed and
connected.
1. Remove 2 screws.
Figure 1-4 Removing the Air Intake Panel
See
1
ADV-8424
Section 1 Installation
13

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

14/20resal

Tabla de contenido