Load Shed Kit - Kohler 14/20RESA Manual Del Usuario

Ocultar thumbs Ver también para 14/20RESA:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 126

1.12.3 Load Shed Kit

An optional load shed kit can be used on single-phase
systems that include a Model RDT or RXT transfer
switch. The load shed kit mounts inside the Model RDT
or RXT transfer switch enclosure. Figure 1-34 shows
the load shed assembly.
The load shed kit provides an automatic load
management system to comply with Section 702.5 of
NEC 2008. The installer is responsible for ensuring that
the power system installation complies with all
applicable state and local codes.
Note: Do not install both a load shed kit and a load
control module (LCM) on the same system.
The load shed kit provides the same load shed and add
functions as the load control module (LCM).
Section 1.12.2.
Note: Connect only non-essential loads to the load
shed kit.
The load shed kit automatically manages up to six
residential loads:
Up to four customer-supplied power relays can be
D
connected through normally open relay contacts on
the circuit board. See TT-1609 for relay coil voltage
specifications.
Two relays are included to control two independent
D
heating, ventilation, and air conditioning (HVAC)
loads.
An adequate electrical supply is required for operation
of the customer-supplied power relays connected to the
load shed kit. Check the electrical requirements of the
customer-provided equipment prior to installation to
determine the wire size and circuit protection required.
Verify that customer-provided equipment complies with
applicable local and national electrical codes.
See TT-1609, provided with the kit, for detailed
installation and connection instructions.
34
Section 1 Installation
All manuals and user guides at all-guides.com
Figure 1-34 Load Shed Assembly GM88281-1
See
3
1. Terminal block TB10
2. Load control circuit board
3. Mounting bracket
Note:
Kit includes current transformer (CT), not shown.
(mounts inside the transfer switch
enclosure)
1
2
GM88281
TP-6803 1/15

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

14/20resal

Tabla de contenido