Generator Set
Note: See Section 1.10.2, Cable Specifications.
1. Generator set terminal block. See Figure 2-4 for location. Check the decal on the generator set for terminal block connections.
2. Connect one end of each cable shield to GROUND at the generator set.
3. Communication cable Belden #8762 or equivalent 20 AWG shielded, twisted-pair cable (one pair).
4. Connect shields together as shown.
5. Leave one end of each cable shield disconnected at the last device.
6. 12 AWG or 14 AWG leads for PWR and COM.
Figure 1-25 Accessory Module Connections with 12--14 AWG Power Leads
28
Section 1 Installation
All manuals and user guides at all-guides.com
2
GND
A
A
RBUS
B
B
PWR
PWR
12 VDC
COM
COM
4
3
6
1
4
3
RXT
A
B
PWR
PWR
COM
COM
PIM
A
B
PWR
PWR
COM
COM
5
A
LCM
B
or load
PWR
shed kit
COM
A
B
A
B
TP-6803 1/15