Prestart Installation Check - Kohler 14/20RESA Manual Del Usuario

Ocultar thumbs Ver también para 14/20RESA:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 126

1.13 Prestart Installation Check

WARNING
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
are in place.
WARNING
Carbon monoxide.
Can
cause
fainting, or death.
The
exhaust
leakproof and routinely inspected.
Generator set operation. Carbon monoxide can cause
severe nausea, fainting, or death. Carbon monoxide is an
odorless, colorless, tasteless, nonirritating gas that can cause
death if inhaled for even a short time. Avoid breathing exhaust
fumes when working on or near the generator set. Never
operate the generator set inside a building. Never operate the
generator set where exhaust gas could seep inside or be
drawn into a potentially occupied building through windows, air
intake vents, or other openings.
Carbon monoxide symptoms.
cause severe nausea, fainting, or death. Carbon monoxide
is a poisonous gas present in exhaust gases.
monoxide is an odorless, colorless, tasteless, nonirritating gas
that can cause death if inhaled for even a short time. Carbon
monoxide poisoning symptoms include but are not limited to
the following:
D Light-headedness, dizziness
D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate
or speak clearly, blurred vision
D Stomachache, vomiting, nausea
If experiencing any of these symptoms and carbon monoxide
poisoning is possible, seek fresh air immediately and remain
active. Do not sit, lie down, or fall asleep. Alert others to the
possibility of carbon monoxide poisoning.
attention if the condition of affected persons does not improve
within minutes of breathing fresh air.
Review the entire installation section. Inspect all wiring
and connections to verify that the generator set is ready
for operation. Check all items in the following Prestart
Checklist.
TP-6803 1/15
All manuals and user guides at all-guides.com
Moving parts.
severe
nausea,
system
must
be
Carbon monoxide can
Carbon
Seek medical
Prestart Checklist
Air Cleaner. Check that a clean air cleaner element is
installed to prevent unfiltered air from entering the
engine. See the generator set operation manual for
instructions.
Air Inlets. Check for clean and unobstructed air inlets.
Battery. Check for tight battery connections. Consult
the battery manufacturer's instructions regarding
battery care and maintenance.
Enclosure.
Check that all enclosure panels and
internal baffling are in place.
Exhaust System.
Check for exhaust leaks and
blockages. Check the muffler condition.
Inspect the exhaust system components for cracks,
D
leaks, and corrosion. Check for tight exhaust system
connections.
Check for corroded or broken metal parts and replace
D
them as needed.
Check that the exhaust outlet is unobstructed.
D
Oil Level. Maintain the oil level at or near, not over, the
full mark on the dipstick.
Operating Area. Check for obstructions that could
block the flow of cooling air. Keep the air intake area
clean. Do not leave rags, tools, or debris on or near the
generator set.
Section 1 Installation