Kohler 14/20RESA Manual Del Usuario página 29

Ocultar thumbs Ver también para 14/20RESA:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 126
Cable Size for PWR and COM Connections
20 AWG Belden #9402 or equivalent, two-pair
20 AWG Belden #1075A or equivalent, two-pair
14 AWG *
12 AWG *
* Use 12 or 14 AWG cable for PWR and COM connections only. For RBUS connections A and B, use shielded, twisted pair communication
cable specified in Section 1.10.2.
Figure 1-23 Total Cable Lengths for PWR and COM Connections
Generator Set
Note: See Section 1.10.2, Cable Specifications.
1. Generator set terminal block. See Figure 2-4 for location. Check the decal on the generator set for terminal block connections.
2. Connect one end of each cable shield to GROUND at the generator set.
3. Communication cable Belden #9402 or equivalent 20 AWG shielded, twisted-pair cable.
4. Connect shields together as shown.
5. Leave one end of each cable shield disconnected at the last device.
Figure 1-24 Accessory Module Communication Connection Details
TP-6803 1/15
All manuals and user guides at all-guides.com
Indoor or
Outdoor
Installation
Indoor
Outdoor
GND
A
A
RBUS
B
B
PWR
PWR
12 VDC
COM
COM
4
3
1
Maximum length per run, meters (ft.)
Number of Modules per Run
1 Module
61
(200)
61
(200)
152
(500)
152
(500)
2
3
A
B
PWR
COM
A
B
PWR
COM
5
A
B
PWR
COM
5
2 Modules
3 Modules
31
(100)
21
31
(100)
21
152
(500)
122
(400)
152
(500)
152
(500)
4
RXT
A
B
PWR
COM
PIM
A
B
PWR
COM
LCM
or load
shed kit
Section 1 Installation
(67)
(67)
27

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

14/20resal

Tabla de contenido