1.7 Fuel Requirements

The generator set operates using natural gas or LPG
fuel. The generator set is EPA-certified for both natural
gas and LPG fuels.
The fuel system installation must comply with the NEC
and local codes.
WARNING
Explosive fuel vapors.
Can cause severe injury or death.
Use extreme care when handling,
storing, and using fuels.
Explosive fuel vapors can cause severe injury or death.
Take additional precautions when using the following fuels:
Propane
(LPG)—Adequate
Because propane is heavier than air, install propane gas
detectors low in a room.
manufacturer's instructions.
Natural Gas—Adequate ventilation is mandatory. Because
natural gas rises, install natural gas detectors high in a room.
Inspect the detectors per the manufacturer's instructions.
Fuel Type
% Load
100%
75%
Natural Gas
50%
25%
100%
75%
LPG
50%
25%
LPG conversion factors:
3
8.58 ft.
= 1 lb.
3
0.535 m
= 1 kg
3
36.39 ft.
= 1 gal.
Figure 1-6 Fuel Consumption
14
Section 1 Installation
All manuals and user guides at all-guides.com
ventilation
is
mandatory.
Inspect the detectors per the
14RESA/RESAL
60 Hz
5.4
(193)
4.7
(163)
3.5
(124)
2.6
(93)
2.3
(81)
2.1
(75)
1.8
(60)
1.2
(45)
Nominal fuel rating:
Natural gas:
LPG:
1.7.1

Fuel Supply

Because of variable climates and geographical
considerations, contact the local fuel supplier for fuel
system planning and installation. Figure 1-5 lists the
recommended fuel ratings and other fuel supply
information for natural gas and LPG fuels.
Verify that the output pressure from the primary gas
utility pressure regulator is within the range shown in
Figure 1-5 and that the utility gas meter flow rate is
sufficient to supply the generator set at rated load plus
all other gas-consuming appliances. For LPG tanks,
verify that the output pressure is as shown in Figure 1-5.
See Figure 1-6 for fuel consumption. Contact the fuel
supplier for flow rate information or a gas meter
upgrade, if necessary.
Fuel type
Fuel supply inlet
Fuel supply pressure,
kPa (in. H
O)
2
Fuel flow rate, maximum, Btu/hr.:
14RESA/RESAL
20RESA/RESAL
Nominal Fuel Rating, Btu/ft.
Natural gas
LPG
Figure 1-5 Fuel Supply
Fuel Consumption, m
50 Hz
4.9
(175)
4.2
(148)
3.1
(108)
2.4
(84)
2.1
(74)
1.9
(68)
1.5
(53)
1.1
(40)
3
3
37 MJ/m
(1000 Btu/ft.
)
3
3
93 MJ/m
(2500 Btu/ft.
)
Natural
Gas
1/2 NPT
1.3--2.7
1.7--2.7
(5--11)
193,000
203,000
281,000
340,000
3
1000
2500
3
/hr. (cfh)
20RESA/RESAL
60 Hz
50 Hz
8.0
(281)
6.4
6.9
(243)
5.4
4.6
(161)
3.9
3.6
(127)
2.9
3.9
(136)
2.9
3.1
(109)
2.4
2.3
(82)
1.8
1.7
(59)
1.3
TP-6803 1/15
LPG
(7--11)
(225)
(189)
(139)
(103)
(102)
(85)
(63)
(47)