3.15 ATS Status Menu
ATS menus appear if a Model RXT transfer switch is
connected to the generator set. If no transfer switch is
connected, or another model ATS is connected to the
engine start connections, Remote ATS is displayed on
the ATS Status screen.
ATS
---->
Status
Figure 3-16 ATS Status Menu, with Calibration
44
Section 3 RDC2 Controller Operation
The ATS Status menu displays Model RXT transfer
switch and source information.
The voltage shown in these menus can be calibrated.
Follow the safety precautions at the beginning of this
manuals. Use a voltmeter to measure the line-to-line
voltage and follow the instructions in Figure 3-16 to
calibrate the voltage readings.
ATS Position:
Normal
Normal Status:
Not/Acceptable
Emerg. Status:
Standby
Single-phase
Normal Volts:
240.0 V
Normal Freq.:
60.0 Hz
Emerg Volts:
240.0 V
Emerg. Freq.:
60.0 Hz
Reset
Calibration
<---- Return
Note: If there is no Model RXT transfer
switch connected to the generator set,
Remote ATS is displayed and the
other screens on this page do not
appear.
Note: Sample data shown.
Three-phase
Normal Voltage:
L1--L2 240 V
Normal Voltage:
L2--L3 240 V
Normal Voltage:
L3--L1: 240 V
Normal Freq.:
60.0 Hz
Normal Rotation:
Similar screens appear for
the emergency source.
Reset
Calib? No
Reset
Calib? Yes
tp6810