6.5 Troubleshooting

Figure 6-4 contains generator set troubleshooting, diagnostic, and repair information. Check for loose connections
before replacing parts.
Problem
Possible Cause
Controller
Backlight turns off after about 1 minute with no
display
activity.
backlight is off.
Controller
Low or no battery voltage.
display is off.
Battery weak or dead.
The generator
set does not
Battery connections reversed or poor.
crank.
Fault shutdown.
Generator set in the OFF mode.
Air cleaner clogged.
The generator
set cranks but
Battery weak or dead.
does not start,
Battery connection poor.
starts hard,
lacks power, or
Spark plug wire connection loose.
operates
Low oil pressure shutdown.
erratically.
Fuel pressure insufficient.
Engine malfunction.
Line circuit breaker in the OFF position.
No AC output.
Line circuit breaker tripping because of
overload.
Line circuit breaker tripping because of short
circuit.
Auxiliary winding circuit breaker tripped.
Low output or
Generator set overloaded.
excessive drop
in voltage.
Generator set
Low oil pressure shutdown.
stops suddenly.
Out of fuel.
Overcrank shutdown.
Auxiliary winding circuit breaker tripped.
Fault shutdown.
Generator set in the OFF mode.
Remote stop command received from a remote
switch, ATS, or OnCuerPlus.
Engine malfunction.
Figure 6-4 General Troubleshooting Chart
TP-6804 1/15
Corrective Action
Backlight will turn on when a button is pressed or the
generator set starts.
Check connections.
Check generator set battery. See Figure 6-4.
Recharge or replace the battery.
Check the connections.
Check the controller display for fault messages. See
Section 2.5. Correct the fault condition and reset the
controller.
Press the RUN button to start the engine or press AUTO
to allow remote starting.
Clean and/or replace the air cleaner.
Recharge or replace the battery.
Clean and tighten the battery connections.
Check the spark plug wires.
Check for oil leaks. Check the oil level and add oil if
necessary.
Check the fuel supply and valves.
Contact an authorized distributor/dealer.
Place the circuit breaker in the ON position.
Reduce the load on the generator set.
Contact an authorized distributor/dealer for service.
Reset the circuit breaker (located in controller's service
access area). Contact an authorized distributor/dealer
for service if breaker trips repeatedly.
Reduce the load.
Check for oil leaks. Check the oil level and add oil if
necessary.
Check fuel supply.
Reset the controller. If the overcrank fault occurs again,
contact an authorized distributor/dealer.
Reset the auxiliary winding circuit breaker. Contact an
authorized distributor/dealer for service if breaker trips
repeatedly.
Check the controller display for fault messages. See
Section 2.5. Correct the fault condition and reset the
controller.
Press the RUN button to start the engine or press AUTO
to allow remote starting.
Check the remote switch position. Check OnCuerPlus.
Contact an authorized distributor/dealer.
Section 6 Troubleshooting
75