Maintenance intervals
The tasks described below may only be carried
out by a qualified electrician.
Select the maintenance intervals with due consideration
of the following aspects:
„ Age and condition of the device
„ Environmental influences
„ Mechanical stress
„ Last test reports
Perform maintenance at least in the following intervals:
Component
Every 6 months
Electrical
Check residual current device, line cir-
switching and
cuit breaker etc. for apparent defects.
safety
Check residual current device for
devices
damage.
Housing inte-
Ensure that the device is clean. Clean
rior
if necessary.
Housing exte-
Check device for defects and dama-
rior
ge.
Ensure that the device is clean. Clean
if necessary.
Î "8.2 Cleaning"
Charging cable
Check charging cable for damage
(for the variant
(e.g. kinks, cracks).
with perma-
Repetition of measurements and tests
nently con-
in accordance with IEC 60364-6 and
nected char-
the applicable national regulations
ging cable)
(e.g. in Germany: DIN VDE 0701/702).
LED Info bar
Check LED information panel for func-
tion and readability.
36
Maintenance work
Component
Every 6 months
Charging socket
Check hinged lid or shutter for func-
(for variant
tion and ease of movement.
with charging
Check the contacts of the charging
socket)
socket for contamination and foreign
objects. If necessary clean charging
socket and remove foreign objects.
Component
Annually
Connection
Check the terminals of the supply line.
terminals
If necessary retighten terminals
Device
Repetition of measurements and tests
according to IEC 60364-6 and the
applicable national regulations (e.g. in
Germany: DIN VDE 0105-100).
f Eliminate damage to the device according to regulati-
ons.
f Document maintenance sufficiently.
f If necessary, request a maintenance protocol from
MENNEKES.
Î "1.1 Service"

8.2 Cleaning

T
DANGER
Risk of fatalities due to electric shock
The device contains electrical components that carry high
voltage. Improper handling of the opened housing, espe-
cially in connection with moisture, will cause severe injury
to persons due to electric shock.
f Clean only the outside of the device.
f Keep the device and protection systems closed.
Maintenance work
Maintenance work