6.4 Switching on the device
T
DANGER
Electric shock hazard when devices are damaged
If a damaged device is used people can be seriously inju-
red or killed through an electric shock.
f Do not use the device if it is damaged.
f Mark the damaged device to ensure that no one conti-
nues using it.
f Eliminate the damage immediately.
f Take the device out of service if necessary.
Precondition:
Device is installed correctly.
Device is in a proper condition.
For versions Professional(+) E 7,4 / 22 only:
The necessary fusing devices (residual current device,
circuit breaker, possibly a shunt release) are incorpo-
rated in the indoor installation, and are functional and
switched on.
Î "5.3.2 Providing fuse protection"
During the initial setting-up process, the device was
inspected in accordance with IEC 60364-6 and the
applicable national regulations (e.g. in Germany: DIN
VDE 0100-600).
Î "6.6 Checking the device"
f Switch on the power supply and check.
Î "6.5 Monitoring the power supply"
9
LED "Standby" is illuminated on the LED information
panel.
6.5 Monitoring the power supply
For versions Professional(+) 7,4 / 22 (PnC) only.
The device is monitored by a phase sequence relay. It
checks the three phase (L1, L2, L3) and the neutral con-
ductor (N) of the power supply for correct phase sequen-
ce, phase failure or undervoltage.
Operating status display
Three phases, clockwise field of rotation:
L3 X
L2 X
f Using terminals L1, L2, L3, N, PE.
L1 X
f Setting relay potentiometer to 3.
SOR74
1
3
9
The green LED is lit.
N X
X 16
15 18
Three phases, anti-clockwise field of rota-
L3 X
L2 X
tion:
L1 X
f Using terminals L1, L2, L3, N, PE.
SOR74
1
3
f Setting relay potentiometer to 3.
N X
9
The green LED is flashing.
X 16
15 18
One phase:
L3 X
L2 X
f Using terminals L1, N, PE.
L1 X
f Setting relay potentiometer to 1.
SOR74
1
3
9
The green LED is lit.
N X
X 16
15 18
The evaluation of the relay potentiometer occurs only
once, after applying the supply voltage.