Resolución de averías
3. Outdoor unit failure mode table
The upper lamp of
Abnormal point
OPERATION INDICTOR
(Failure mode / protection)
lamp(Indoor unit)
OFF
None (Normal)
2-time flash
Outdoor power system
2.5 seconds OFF
3-time flash
Discharge temperature thermistor
2.5 seconds OFF
Defrost thermistor
Fin temperature thermistor
P.C. board temperature thermistor
4-time flash
Overcurrent
2.5 seconds OFF
Compressor synchronous
abnormality (Compressor start-up
failure protection)
5-time flash
Discharge temperature
2.5 seconds OFF
6-time flash
High pressure
2.5 seconds OFF
7-time flash
Fin temperature/ P.C. board
2.5 seconds OFF
temperature
9-time flash
Nonvolatile memory data
2.5 seconds OFF
10-time flash
Discharge temperature
2.5 seconds OFF
11-time flash
DC voltage
2.5 seconds OFF
Each phase current of compressor
12-time flash
Overcurrent
2.5 seconds OFF
Compressor open-phase
14-time flash
Stop valve
2.5 seconds OFF
(Closed valve)
NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (11-3.).
278
LED indication
Condition
(Outdoor P.C. board)
Over current protection stop is
continuously performed three times
within 1 minute after the compressor
gets started.
1-time flash every
Thermistor shorts or opens
2.5 seconds
during compressor running.
3-time flash
2.5 seconds OFF
4-time flash
2.5 seconds OFF
11-time flash
12A(MUZ-HC25)/ 14A(MUZ-HC35)
2.5 seconds OFF
current flow into intelligent
power module.
12-time flash
Waveform of compressor current
2.5 seconds OFF
is distorted.
Temperature of discharge
temperature thermistor exceeds 116
compressor stops.
Compressor can restart if discharge
temperature thermistor reads 100
less 3 minutes later.
Temperature of indoor coil
thermistor exceeds 70
When defrost thermistor exceeds 70
in COOL mode.
7-time flash
Temperature of fin temperature
2.5 seconds OFF
thermistor on the inverter P.C. board
exceeds 82: (MUZ-HC25)/83
(MUZ-HC35), or temperature of P.C.
board temperature thermistor on the
inverter P.C. board exceeds 81
(MUZ-HC25)/ 85: (MUZ-HC35).
Nonvolatile memory data cannot
5-time flash
2.5 seconds OFF
be read properly.
Temperature of discharge tempe-
rature thermistor has been 50
for 20 minutes.
8-time flash
DC voltage of inverter cannot be
detected normally.
2.5 seconds OFF
9-time flash
Each phase current of compressor
cannot be detected normally.
2.5 seconds OFF
10-time flash
12A(MUZ-HC25)/ 14A(MUZ-HC35)
2.5 seconds OFF
current flow into intelligent
power module (IPM).
When the open-phase operation of
compressor is detected.
When the interphase short out occurs in
the output of the intelligent power
module (IPM).
When the compressor winding shorts out.
Closed valve is detected by compressor
14-time flash
current.
2.5 seconds OFF
Correspondence
•Reconnect connectors.
•Refer to 11-5. A "How to
check inverter/
compressor".
•Check stop valve.
•Refer to 11-5.G "Check
of outdoor thermistors".
❈Defective outdoor
thermistors can be
identified by checking
the blinking pattern
of LED.
•Reconnect compressor
connector.
•Refer to 11-5.A "How to
check inverter/
compressor".
•Check stop valve.
•Reconnect compressor
connector.
•Refer to 11-5.A "How to
check inverter/
compressor".
•Check refrigerant circuit
°C
,
and refrigerant amount.
°C
or
•Check refrigerant circuit
°C
in HEAT mode.
and refrigerant amount.
°C
•Check stop valve.
•Check around outdoor unit.
•Check outdoor unit air
°C
passage.
•Refer to 11-5.I "Check of
outdoor fan motor".
°C
•Replace the inverter P.C.
board.
•Check refrigerant circuit
°C
or less
and refrigerant amount.
•Refer to 11-5.A "How to
check inverter/
compressor".
•Reconnect compressor
connector.
•Refer to 11-5. A "How to
check inverter/
compressor".
•Check stop valve.
Indoor/outdoor
Outdoor unit
unit failure mode
failure mode
recall function
recall function